Bulletin No. 50006-519-01BDecember 1996Chapter 6 — Class 8839 ALTIVAR <strong>56</strong> Combination DevicesControl WiringCONTROL WIRINGTable 50: Control Terminal Strip Characteristics (Power Circuit W)Terminal [1] [2] Function Characteristics1 LO1 (Logic Output 1) 24 V, 200 mA max. [5]2 LO2 (Logic Output 2) 24 V, 200 mA max. [5]3 COM (Logic Common) 0 V4 +24 (+24 V Control Supply)5 LI1 (Logic Input 1)6 LI2 (Logic Input 2)7 LI3 (Logic Input 3)Minimum: 12 V; Maximum: 30 VQuiescent current: 15 mA typicalIs = 210 mA max. [5]24 V, 10 mAState 0: V < 5 V; State 1: V > 12 V; Vmax = 30 V24 V, 10 mA;State 0: V < 5 V; State 1: V > 12 V; Vmax = 30 V24 V, 10 mA;State 0: V < 5 V; State 1: V > 12 V; Vmax = 30 V8 LI4 (Logic Input 4)24 V, 10 mA;State 0: V < 5 V; State 1: V > 12 V; Vmax = 30 V9 +10 V Reference Supply 10 V, Is = 10 mA max.10 AI1 (Analog Input 1: Speed Reference Voltage) 0-10 V, Z = 30 kΩ11 COM (Speed Reference Common) 0 V12 GND, S (Ground/Shield)13 AI2 (Analog Input 2: Speed Reference Current) 4-20 mA [6] , Z = 250 Ω14 COM (Analog Common) 0 V15 AO1 (Analog Output 1)0-20 mA, 12 V max. (programmable as 4-20 mAw/ keypad display)16 Auxiliary Terminal [7] Terminal jumpered to Terminal 417 +115 V (Control Transformer) [7]18 115 V Rated Terminal [7]19 GND (Control Transformer) [7]2021120 V SPR Relay Coil 21 [7] 115-120 V/60 Hz supply (user-supplied)222324 [4]25R1 Relay, N.C. Contact (Fault Relay Output)R2 Relay, N.O. Contact (Run Relay Output)26Auxiliary Contact (AFC Mode Status)27[7][1] See control circuit diagrams on pages 151 and 152.Minimum: 10 mA, 24 VDCMaximum inductive load of:• 2.0 A, 120 VAC; Max: 0.10 J/operation,80 operations/minute• 1.0 A, 220 VAC; Max: 0.25 J/operation,25 operations/minute• 2.0 A, 24 VAC; Max: 0.10 J/operation,80 operations/minuteArc suppression provided by varistors in parallelw/ relay contacts.Minimum: 10 mA, 24 VDCMaximum inductive load of:• 2.0 A, 120 VAC; Max: 0.10 J/operation,80 operations/minute• 1.0 A, 220 VAC; Max: 0.25 J/operation,25 operations/minute• 2.0 A, 24 VAC; Max: 0.10 J/operation,80 operations/minuteArc suppression provided by varistors in parallelw/ relay contacts.• 15 A, 125 VAC• 10 A, 250 VAC[2] All terminals are rated 600 V, 30 A (Class 9080, Type GM6). Maximum wire size for all terminals is 10 AWG (2.5 mm 2 ).[3] Relay coil deenergizes on fault.[4] Contact state with drive controller deenergized.[5] Total current of +24 V internal supply is 210 mA. Available current of the two logic outputs can be calculated as follows: eachinput requires 10 mA, each analog output requires 20 mA and the typical quiescent current of LOP is 15 mA.[6] 0-20 mA, x-20 mA, 20-4 mA programmable with keypad display. 0-5 V (Z = 30 kΩ) selectable with switch on control board.[7] Available only when options are included.© 1996 Square D All Rights Reserved135ηττπ://νιχοντρολσ.χοm

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!