Bulletin No. 50006-519-01BDecember 1996Chapter 6 — Class 8839 ALTIVAR <strong>56</strong> Combination DevicesControl WiringTable 51: Control Terminal Strip Characteristics (Power Circuits Y & Z)Terminal [1] [2] Function Characteristics26 [7]2728 [3]2930 [4]3132 [7]33120 V SPR Relay Coil (if used) 115 - 120 V / 60 Hz supply (user-supplied)R1 Relay, N.C. Contact (Fault RelayOutput)R2 Relay, N.O. Contact (Run RelayOutput)Auxiliary Contact (AFC Mode Status)Minimum: 10 mA, 24 VDCMaximum inductive load of:• 2.0 A, 120 VAC; Max: 0.10 J/operation,80 operations/minute• 1.0 A, 220 VAC; Max: 0.25 J/operation,25 operations/minute• 2.0 A, 24 VAC; Max: 0.10 J/operation,80 operations/minuteArc suppression provided by varistors in parallelw/ relay contacts.Minimum: 10 mA, 24 VDCMaximum inductive load of:• 2.0 A, 120 VAC; Max: 0.10 J/operation,80 operations/minute• 1.0 A, 220 VAC; Max: 0.25 J/operation,25 operations/minute• 2.0 A, 24 VAC; Max: 0.10 J/operation,80 operations/minuteArc suppression provided by varistors in parallelw/ relay contacts.• 15 A, 125 VAC• 10 A, 250 VAC[1] See control circuit diagrams on pages 153 - 1<strong>56</strong>.[2] All terminals are rated 600 V, 30 A (Class 9080, Type GM6). Maximum wire size for all terminals is 10 AWG(2.5 mm 2 ). Tightening torque 7 - 8 lb-in (0.8 - 0.9 N•m).[3] Relay coil deenergizes on fault.[4] Contact state with drive controller deenergized.[5] Total current of +24 V internal supply is 210 mA. Available current of the two logic outputs can be calculated asfollows: each input requires 10 mA, each analog output requires 20 mA and the typical quiescent current ofLOP is 15 mA.[6] 0 - 20 mA, x - 20 mA, 20 - 4 mA programmable with keypad display. 0 - 5 V (Z = 30 kΩ) selectable with switchon control board.[7] Available only when options are included.[8] On when bypass contactor is energized.© 1996 Square D All Rights Reserved137ηττπ://νιχοντρολσ.χοm

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!