Chapter 5 — ConfigurationBulletin No. 50006-519-01B7 →General Configuration Menu December 1996Controlled Stop CommandMethods (continued)Two adjustable parameters, DC Injection Level and DC Brake Time, control theoperation of DC Injection Braking. DC Injection Level sets the current level usedfor injection braking. The level is programmable between 50 and 110% of nominaldrive controller current. Factory setting is 70%. Actual braking torque depends onthe motor characteristics. DC Brake Time can be set between 0 and 30 seconds,preset at 2 seconds. If 30.1 seconds is selected, the drive controller brakes for 30seconds at the adjusted level and then continuously at 50% of rated current.1Run Forward0Controlled Stop 1LIx Active 0State HighFrequency outputf0.1 HzDC injectionIdcTdc