Chapter 2 — WiringBulletin No. 50006-519-01BPower Wiring December 1996POWER WIRINGTable 8: Power Terminal Strip Characteristics [1]Connector Terminal [2] Function CharacteristicsGNDL1L2L33-phase powersupply460 VAC ±15% (ATV<strong>56</strong>•••N4 units)208 V ±10% / 230 V ±15% (ATV<strong>56</strong>•••M2 units)47 to 63 Hz+–FilteredDC voltage620 to 850 VDC (ATV<strong>56</strong>•••N4 units)275 to 425 VDC (ATV<strong>56</strong>•••M2 units)J2U/T1V/T2W/T3GNDOutputconnections tomotor0 to 460 VAC0 to 208 VAC / 0 to 230 VACCL1 [3]CL2Single-phasecontrol supply460 VAC ±15% (ATV<strong>56</strong>•••N4 units)208 V ± 10% / 230 V ± 15% (ATV<strong>56</strong>•••M2 units)47 to 63 HzPAPBReservedReserved. Do not wire to PA, PB terminals.CL21CL22Tap for CL1 andCL2460 VAC ±15% (ATV<strong>56</strong>•••N4 units)208 V ± 10% / 230 V ± 15% (ATV<strong>56</strong>•••M2 units)47 to 63 HzATV<strong>56</strong>D16N4 to D79N4 drive controllers only[1] For power terminal strip locations, refer to Figure 9 on page 22.[2] See circuit diagrams on page 28 and 29.[3] The CL1 and CL2 terminals are connected with jumpers to L1 and L2 terminals. When using a line contactor,the jumpers must be removed and CL1 and CL2 supplied separately to maintain control power. See circuitdiagrams on page 28 and page 29. CL1 and CL2 must be connected to the same feeder conductors that supplyL1, L2 and L3 of the drive controller.20 © 1996 Square D All Rights Reservedηττπ://νιχοντρολσ.χοm

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!