eWON General Reference Guide - eWON wiki
eWON General Reference Guide - eWON wiki
eWON General Reference Guide - eWON wiki
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Supported memory areas:<br />
Modifier:<br />
<strong>General</strong> <strong>Reference</strong> <strong>Guide</strong> IO Servers Configuration<br />
(*) Important: To avoid loss of precision due to Integer to float conversion, choose the right storage DataType for your Tag.<br />
See "DataType of Tags" on page 75<br />
examples:<br />
• Status register:<br />
The STATUS Tag is a special Tag that returns information about the current state of communication for a given device. As for the other Tags, the<br />
status Tag ValueName is composed of:<br />
Status, Global Device Address<br />
• You can define a status Tag for each PLC used.<br />
• If you use the status address, the Tag must be configured as analog.<br />
0<br />
X Memory area<br />
A Auxiliary area<br />
C Counter area<br />
CIO Core I/O area<br />
D Data Memory area<br />
E Extended Data Memory area<br />
H Holding area<br />
T Timer Area<br />
W Work Area<br />
Table 90: FINS IO server supported memory areas table<br />
Symbol Modifier value range<br />
Automatic<br />
Tag type<br />
W Word (default) 0 .. 65535 DWord<br />
S signed Word -32768 .. 32767 Integer<br />
D DWord 0 .. 4294967296 (*) DWord<br />
L signed DWord -2147483648 .. 2147483647 (*) Integer<br />
F Float +/- 3.4e38 Float<br />
Table 91: FINS Modifiers<br />
address point to<br />
A5 the Word at address 5 in the Auxiliary Area (equivalent to AW5)<br />
AS5 the Signed Word at address 5 in the Auxiliary Area<br />
A2#5 the bit 5 from the Word at address 2 in the Auxiliary Area<br />
E0:S3 the signed Word at address 3 from the Extended Data Memory 0<br />
C5 the Counter at address 5<br />
D4 the Data Memory at address 4<br />
Table 92: FINS address examples<br />
Communication not initialized. Status UNKNOWN.<br />
If no Tag is polled on that device address, the communication status is unknown.<br />
1 Communication OK.<br />
2 Communication NOT OK.<br />
Table 93: Tag Status meaning<br />
RG-001-0-EN ver 1.14 <strong>eWON</strong>® - 02/05/2012 - ©<strong>eWON</strong> sa Page 118