eWON General Reference Guide - eWON wiki
eWON General Reference Guide - eWON wiki
eWON General Reference Guide - eWON wiki
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
The parameters for Alarm traps are as follows:<br />
3.3.2.8 Data Management<br />
Figure 22: Data Management config page<br />
<strong>eWON</strong> can upload automatically historical data to the eSyncDMserver.<br />
The upload can occur:<br />
• on a defined interval<br />
• on a complex schedule<br />
• on alarm<br />
• on a trigger from the Basic program<br />
<strong>General</strong> <strong>Reference</strong> <strong>Guide</strong> <strong>eWON</strong> Configuration<br />
Param 0 Tag name (Text [0..63])<br />
Param 1 Alarm message (Text [0..255])<br />
Param 2 Value of the Tag in alarm (Integer 32bits)<br />
Param 3 Alarm status (Integer)<br />
Param 4 Alarm Type (Integer)<br />
Table 17: Alarm traps parameters<br />
Control Description<br />
<strong>eWON</strong> Data Management ID <strong>eWON</strong> Identifier specified on the eSyncDM server (mandatory)<br />
Password Password to access the <strong>eWON</strong> account on the server (may be empty)<br />
Server URL<br />
Upload interval<br />
Advanced data transfert schedule<br />
Selected Group(s)<br />
Upload on alarm<br />
Address and port of the eSyncDM. Could be an IP address or an URL<br />
If port is omitted, 80 will be used.<br />
ex: 10.0.120.251 or data.myserver.com:8080<br />
The interval in minutes between each upload of data<br />
Set to 0 if you want to use the "Advanced data transfert schedule" or upload<br />
upon alarm<br />
Schedule the upload the same way as "Task Planner"<br />
see "Task Planner" on page 16 to complete syntax description<br />
ex: 0 */6 * * * will upload every 6 hours (at 0, 6, 12 and 18 o’clock)<br />
Data management sends only tags belonging to group. Select which group(s)<br />
you want to upload.<br />
When selected, the upload will be triggered also when one of the tags of the<br />
selected groups rises an alarm.<br />
Table 18: Data Management parameters<br />
RG-001-0-EN ver 1.14 <strong>eWON</strong>® - 02/05/2012 - ©<strong>eWON</strong> sa Page 25