5.13.2.3 COM configuration (MPI port)<br />
<strong>General</strong> <strong>Reference</strong> <strong>Guide</strong> IO Servers Configuration<br />
Figure 112: MPI link configuration<br />
Parameter Description<br />
Protocol Type<br />
Baud Rate<br />
Select protocol PPI MULTIMASTER.<br />
As the MPI port configuration is shared by the S7-200 and the S73&400<br />
IOServers, this combo box shows also the MPI & Profibus protocols.<br />
PPI MultiMaster and MPI/Profibus are mutually exclusive. It is not allowed to<br />
use at the same time the S7-200 and the S73&400 IOServers on the MPI<br />
port.<br />
Speed of the MPI port.<br />
Available speeds are:<br />
• disable<br />
• 9.6 kBauds<br />
• 19.2 kBauds<br />
• 45.45 kBauds<br />
• 93.75 kBauds<br />
• 187.5 kBauds<br />
• 1.5 MBauds<br />
• 3 MBauds (only for 2005CD-MPI or 4005CD-MPI)<br />
• 6 MBauds (only for 2005CD-MPI or 4005CD-MPI)<br />
• 12 MBauds (only for 2005CD-MPI or 4005CD-MPI)<br />
Reply Timeout The maximum time the <strong>eWON</strong> will wait for a valid MPI message response<br />
PPI MultiMaster Address The device address of <strong>eWON</strong> on PPI link (0..126, default is 0)<br />
PPI Highest Station Address<br />
The highest station address polled by <strong>eWON</strong>. Select between 15, 31, 63 or<br />
127.<br />
Figure 113: PPI MultiMaster settings<br />
Note: When using the PPI MultiMaster, the status counters to be checked are the MPI counters and not the PPI counters.<br />