5.10 <strong>eWON</strong> IO Server<br />

5.10.1 Introduction<br />

The <strong>eWON</strong> IO server is used to interface the <strong>eWON</strong> INPUTS and OUTPUTS.<br />

Depending on your <strong>eWON</strong> model, you have:<br />

<strong>eWON</strong> types<br />

<strong>General</strong> <strong>Reference</strong> <strong>Guide</strong> IO Servers Configuration<br />

Additionally, there are a number of Tags that can be addressed with this IO server and which are computed by the <strong>eWON</strong> IO Server.<br />

These additional Tags are used for energy management. In Energy management, the following requirements are taken into accounts:<br />

• Using digital inputs as counter inputs<br />

• Count for a given interval and latch computed result (also save it in historical)<br />

• Reject the measurement interval if too long or too short<br />

• Adjust the <strong>eWON</strong>’s Real Time Clock based on a digital input<br />

These Tags will be computed if the energy module is enabled.<br />

There is no topic name to define for the <strong>eWON</strong> IO server.<br />

5.10.2 Standard <strong>eWON</strong> I/O Item Names<br />

500, x001, x101,<br />

x005[CD], x104<br />

5.10.2.1 Tag name convention<br />

The following Tags are available for standard <strong>eWON</strong> Inputs & Outputs access:<br />

NOTE:<br />

The button input (BI1) can be used during normal <strong>eWON</strong> operations, if it is pressed for more than 4 seconds while the <strong>eWON</strong> is<br />

booting, the flash file system will be erased (please refer to chapter “Resetting the <strong>eWON</strong>” on page 218).<br />

(1) The number of items depends of the <strong>eWON</strong> type. See Table 106 on page 128.<br />

(2) From firmware 4.1S3 to 4.3, the CIx value wrapped at 1.000.000. Before 4.1S3, the CIx was misinterpreted as negative when<br />

value passes over 231 .<br />

RG-001-0-EN ver 1.14 <strong>eWON</strong>® - 02/05/2012 - ©<strong>eWON</strong> sa Page 127<br />

4002<br />

Digital Inputs 1 9<br />

Digital Outputs 1 3<br />

Analog Inputs 0 6<br />

Table 103: <strong>eWON</strong> Inputs/Outputs<br />

IO Server configuration Comment<br />

IO Server Name EWON<br />

Topic Name Empty<br />

Item Name DI# Digital Input (1) Boolean<br />

CI# Counter Input (1) 0 to 2.147.400.000(2) Analog<br />

FI# Counter Input 0 to 255 Analog<br />

LI# Latched Counter Input (1) Analog<br />

DO# Digital Output (1) Boolean<br />

AI# Analog Input (1) Analog<br />

BI# Button Input (1) Boolean<br />

Table 104: <strong>eWON</strong> IO server configuration parameters - no topic defined