5.10.2.3 Analog Input Value Range (<strong>eWON</strong>4002)<br />

<strong>General</strong> <strong>Reference</strong> <strong>Guide</strong> IO Servers Configuration<br />

The Analog Inputs (AI1 to AI6) come from a 12 bits ADC. Then, the values read on a AI# tag go from 0 to 4095.<br />

5.10.2.3.1 Configurable analog input AI1 to AI4<br />

• In 0-10V mode<br />

AI# Volt<br />

0 0<br />

4095 10<br />

If you need to read the Tag value converted in Volt, you can set a factor of 0.0024420 = 10/4095 with an offset of 0.<br />

Figure 102: Tag’s configuration: reading the tag value in Volt<br />

• In 0-20 mA mode<br />

The shunt resistor for measuring current is a 220 Ohm.<br />

AI# mA<br />

0 0<br />

1802 20<br />

If you need to read the Tag value converted in mA, you can set a factor of 0.011099 = 20/1802 with an offset of 0.<br />

Figure 103: Tag’s configuration: reading the tag value in mA<br />