eWON General Reference Guide - eWON wiki
eWON General Reference Guide - eWON wiki
eWON General Reference Guide - eWON wiki
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>General</strong> <strong>Reference</strong> <strong>Guide</strong> IO Servers Configuration<br />
5.12.2.2 Advanced Routing Setup<br />
Advanced Routing Setup is a feature that has been introduced from firmware version 6.3 onwards.<br />
It allows to access devices that make part of an other MPI/Profibus network connected indirectly to the <strong>eWON</strong> through another (or various other)<br />
PLC(s).<br />
Advanced Routing Setup items are visible when the Enable checkbox is ticked.<br />
Note: Parameters that would have been set in this section remain in memory but are visually hidden AND not taken into account by the firmware<br />
when the Enable checkbox is unticked.<br />
Figure 107: Advanced MPI configuration screenshot<br />
Parameter Description Default value<br />
Advanced Routing Setup Enable/disable Advanced Routing Setup feature 0 (disabled)<br />
Gateway/Destination<br />
S7-Subnet ID:<br />
Used when no subnet ID is specified in the ISOTCP<br />
message to relay on the MPI bus<br />
ISOTCP S7-Subnet ID: <strong>eWON</strong> subnet ID at the ISOTCP interface side<br />
Table 110: Advanced MPI/Profibus routing configuration parameter description<br />
0000-0000<br />
0000-0000<br />
(invalid subnet ID)<br />
MPI/PROFIBUS S7-Subnet ID: <strong>eWON</strong> subnet ID at the MPI interface side 0000-0000<br />
Default Next MPI/PROFIBUS Node:<br />
Gateway Entry 1..3<br />
Destination S7-Subnet ID<br />
Gateway Entry 1..3<br />
Next MPI/Profibus Node ID<br />
MPI node of the PLC towards which the MPI messages will<br />
be sent out if the destination subnet ID specified is not the<br />
one of the <strong>eWON</strong> (see previous field), nor one of the ones<br />
specified in the gateway entries (see next fields)<br />
MPI messages with destination subnet ID equal to this<br />
destination ID will be forwarded to the next MPI/Profibus<br />
Node (see next field)<br />
RG-001-0-EN ver 1.14 <strong>eWON</strong>® - 02/05/2012 - ©<strong>eWON</strong> sa Page 137<br />
2<br />
0000-0000<br />
See previous row 2