3.4 Tag Setup<br />

3.4.1 Tag definition: Introduction<br />

The <strong>eWON</strong> Monitoring Web Interface features are based on:<br />

• The configurable monitoring of Tags<br />

• The execution of scripts<br />

<strong>General</strong> <strong>Reference</strong> <strong>Guide</strong> <strong>eWON</strong> Configuration<br />

All the variables monitored by the <strong>eWON</strong> are defined as "Tags". A Tag is a value changing with time and coming from a data-source.<br />

Typical data-sources are:<br />

• <strong>eWON</strong> internal Inputs/Outputs<br />

• Remote Inputs/Outputs (modbus, UnitelWay, DF1, MPI, ...)<br />

• <strong>eWON</strong> memory Inputs/Outputs (updated by script)<br />

The data source is called an "IO Server". An IO Server is the interface between the changing value and the <strong>eWON</strong> monitoring engine. It is a kind<br />

of driver. Any variable from any data source must have a common representation for all IO Servers in order to define common interface in the<br />

<strong>eWON</strong>.<br />

The data-source representation in the <strong>eWON</strong> uses 3 fields for the definition of a Tag:<br />

• The IO Server Name<br />

• The Topic name<br />

• The Item Name<br />

A Tag’s data-source will be uniquely identified with these 3 parameters.<br />

IO Server name<br />

Topic Name<br />

Item Name<br />

For example, the MODBUS IO Server needs to poll registers or coils from a slave, so it uses an item name representation to define the register<br />

type, register address and slave address. (Example "40001,5" => Where 4 means read write register, 0001 is the register number and 5 is the<br />

slave Modbus address).<br />

A description of the different IO Server syntax is given in chapter "The <strong>eWON</strong> IO Servers" on page 94. Once a Tag is configured with its Server<br />

Name, Topic Name and Item Name, it is given a Tag name that will be used everywhere in the <strong>eWON</strong>.<br />

3.4.1.1 DataType of Tags<br />

Internally, all Tags are stored on 4 bytes and represent:<br />

• a single precision FLOATING POINT format (IEEE float representation)<br />

• a DWORD, an unsigned 32 bits integer<br />

• an INTEGER, a signed 32 bits integer<br />

• a BOOLEAN, a binary value<br />

In addition, an Automatic choice is provided to let <strong>eWON</strong> store the value of the<br />

tag in the best of the above DataTypes (depending of the IOServer register/<br />

modifier type).<br />

Is a kind of driver name. For each IO Server there is a specific Topic Name and Item Name<br />

syntax. The following drivers are available: MODBUS, EWON, MEM, NETMPI, UNITE<br />

(Unitelway), DF1, FINS, S7 3&400(MPI), S7 200(PPI) and S5-AS511.<br />

Is used to group items inside an IO Server, for example the memory an IO Server uses the<br />

blank topic ("") and the retentive topic ("ret"). All the Tags of the MEM IO Server defined in the<br />

"ret" topic will have their value saved and restored when the <strong>eWON</strong> boots. All the IO servers<br />

do not use Topic Name. In that case Topic Name must be empty.<br />

The item name is a string of characters; its syntax is specific to each IO Server. The Item<br />

Name describes the physical variable to monitor using the IO Server.<br />

Table 48: Tag’s data-source parameters<br />

The DWORD and INTEGER types are available only since firmware 6.0.<br />

Before firmware 6.0, all the tags were stored in single precision FLOAT format (IEEE float representation), and only 2 types were available<br />

(Analog and Boolean). This means that you can only expect a maximum precision of 7 decimal digits.<br />

That’s why, before Firmware6.0, the 32 bits Integer data read by an IOServer were automatically converted in the nearest float number<br />

representation.<br />

For a huge number, it will mean a truncation (ex: integer value 1600000015 will be stored as float 1600000000.0).<br />

RG-001-0-EN ver 1.14 <strong>eWON</strong>® - 02/05/2012 - ©<strong>eWON</strong> sa Page 75