Alstom Proposal # SD22007, CR3 EPU Turbine Generator Retrofit MeetinP Notes, 05/15/07: Pg. 5 of 7<br />

Engineering: Comments:<br />

0 Provide estimated megawatt output vs. condenser pressure curve for the 57” LSB (16.8M2) LP turbine. Include on curve provided for the<br />

47” LSB (12.9M2) LPturbine provided in proposal (pg. 209).<br />

- Re: See pg. 2. Paul will email curve.<br />

0 47” LSB LP turbine appears to choke at 2.2 In Hg. 47” LSB appears marginal for 1100 MWe output with 4 exhaust flows.<br />

&Correct.<br />

0 Has a 57”LSB LP turbine been retrofitted into a Westinghouse turbine frame? References are on pg. 43.<br />

- Re: Diablo Canyon. Actual performance was much greater than predicted. Guaranteed 35 MW. Obtained 46 at unit 1 and 50 at unit 2.<br />

0 Why was a full impulse HP turbine design selected? Is design constrained due to reuse of existing inlet nozzle box?<br />

- Re: Standard design in Europe.<br />

0 Should HP and LP turbine bearing be rebabbitted due to new rotor journals?<br />

Re: Request to include in proposal.<br />

0 Why is bearing 5 loaded greater than bearing 4 following retrofit (pg. 196)?<br />

Re: Unknown at meeting.<br />

0 Pg. 538 discusses bearing pedestal modification for reinforcing brackets. What is expected? Are modifications required?<br />

Re: Bearing strongback to withstand L-0 blade failure by using stronger bolts and heavier strongback if needed.<br />

Generator rotor rewind will reuse the existing rotor copper winding with new insulation. What is the rewound rotor current capacity rating?<br />

- Re: 7,720 Amps @ 75 psi H2 gas pressure.<br />

Generator mid-section replacement is rated at 1173 MVA. What is the rating limiting component? What is the excitation current required?<br />

Re: Rotor is limiting above 1173 MVA. Excitation requirement is 6,770 amps @ max PF.<br />

Generator stator rewind is rated at 1162.5 MVA. Excitation current required is 6,845A (pg. 120). What is the rating limiting component? Pg.<br />

119 states field measurement confirmation is required. What is the risk? The capability curve is shown on pg. 121. Why isn’t the maximum<br />

power output at unity power factor on the curve?<br />

Re: Stator core is limiting for 1162.5 MVA stator rewind.<br />

The generator stator rewind reuses the existing core iron as is. What engineering evaluations were performed to qualify reuse of the existing<br />

core iron?<br />

- Re: Engineering models were evaluated.<br />

Is a generator startup ventilation test requires for either generator options?<br />

Re: A ventilation test is not required based on experience.<br />

What are the customer installation requirements for the stator cooling water skid and the static excitation system? Pg. 73 states the water<br />

skid and water tank control system is not included? What does this mean?<br />

Re: The proposal statement in not applicable.<br />

0 What load rating will the lifting beam have?<br />

- Re: Design rating should be for generator rotor 360,000 lbs. Lifting slings are included.<br />

PEF-NCR-0 1347