Domestic Hot Water<br />
For bathrooms on the site, hot water will be generated by a local<br />
point <strong>of</strong> use storage-type electric water heater. The tank will be<br />
located near the fixtures served to eliminate the requirements for<br />
temperature maintenance.<br />
140º F water will be provided to scullery and rinsing sinks. A<br />
thermostatic mixing valve will reduce the temperature to 120º F<br />
to feed the hand sinks. Floor drains will be provided for general<br />
cleaning purposes.<br />
• Size each heater based on a modified Hunters Curve<br />
and anticipated fixture unit count. Special equipment<br />
demands such as dishwashers shall be added to the<br />
water heater load.<br />
• Size the hot water supply and return lines not to exceed<br />
10°F heat loss. Dead ends shall be limited to 20-ft.<br />
• Provide combination shut-<strong>of</strong>f and balancing valves in the<br />
hot water return circulating lines.<br />
• Provide insulation on all domestic hot water supply,<br />
horizontal cold water piping and return circulation<br />
piping.<br />
All piping shall be insulated per the most stringent requirements<br />
found in the codes and standards referenced in the general<br />
section.<br />
Plumbing Fixtures<br />
All fixtures shall be provided with individual stop valves. Water<br />
closets shall be furnished with flush valves and lavatories will be<br />
provided with electronic faucets.<br />
• Plumbing fixture accessibility clearances, installation and<br />
accessories shall be ADA compliant.<br />
• Plumbing fixtures shall be ultra-low flow water<br />
conserving/saving type fixtures, faucets and valves.<br />
• Plumbing fixtures in public areas shall have motion/<br />
user sensing devices (with manual by-pass) for fixture<br />
operation.<br />
• Drinking fountains shall be provided as indicated on the<br />
architectural plans and as required by Code.<br />
• Scald control systems shall be provided in all showers.<br />
MICHAEL MALTZAN ARCHITECTURE, INC. 3 - 99