Domestic Hot Water<br />

For bathrooms on the site, hot water will be generated by a local<br />

point <strong>of</strong> use storage-type electric water heater. The tank will be<br />

located near the fixtures served to eliminate the requirements for<br />

temperature maintenance.<br />

140º F water will be provided to scullery and rinsing sinks. A<br />

thermostatic mixing valve will reduce the temperature to 120º F<br />

to feed the hand sinks. Floor drains will be provided for general<br />

cleaning purposes.<br />

• Size each heater based on a modified Hunters Curve<br />

and anticipated fixture unit count. Special equipment<br />

demands such as dishwashers shall be added to the<br />

water heater load.<br />

• Size the hot water supply and return lines not to exceed<br />

10°F heat loss. Dead ends shall be limited to 20-ft.<br />

• Provide combination shut-<strong>of</strong>f and balancing valves in the<br />

hot water return circulating lines.<br />

• Provide insulation on all domestic hot water supply,<br />

horizontal cold water piping and return circulation<br />

piping.<br />

All piping shall be insulated per the most stringent requirements<br />

found in the codes and standards referenced in the general<br />

section.<br />

Plumbing Fixtures<br />

All fixtures shall be provided with individual stop valves. Water<br />

closets shall be furnished with flush valves and lavatories will be<br />

provided with electronic faucets.<br />

• Plumbing fixture accessibility clearances, installation and<br />

accessories shall be ADA compliant.<br />

• Plumbing fixtures shall be ultra-low flow water<br />

conserving/saving type fixtures, faucets and valves.<br />

• Plumbing fixtures in public areas shall have motion/<br />

user sensing devices (with manual by-pass) for fixture<br />

operation.<br />

• Drinking fountains shall be provided as indicated on the<br />

architectural plans and as required by Code.<br />

• Scald control systems shall be provided in all showers.<br />

MICHAEL MALTZAN ARCHITECTURE, INC. 3 - 99