<strong>Planning</strong> <strong>with</strong> LDA/LDC4.2 System components4.2.9 Incoming cable connection unitIf power needs to be supplied to the busbar trunking system via cables, you should use anLDA(C)....-KE incoming cable connection unit.Figure 4-7Incoming cable connection unitThe incoming cable connection unit is designed for the following rated currents:● 1100 to 2600 A (<strong>with</strong> IP34)● 900 to 2100 A (<strong>with</strong> IP54)Enclosure sizesDepending on the system, three sizes can be selected:Size 1:Size 2:Size 3:LDA1...-KE to LDA2...-KELDA3...-KE and LDA4...-KELDC2...-KELDA5...-KE.The maximum dimensions are 920 mm x 639 mm x 490 mm (W x H x D).IP34 or IP54 degree of protection can be selected.You can connect single-core or multi-core cables. You can connect cross sections up to300 mm 2 (bolted connection) directly to the incoming cable connection unit bars.The sheet steel flange plates and the cable sleeves are included in the scope of supply ofthe standard product. Single-core cables are supplied <strong>with</strong> an undrilled aluminium plate forcable entry.<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong><strong>Planning</strong> Manual, 10/2007, A5E01541101-01 119