<strong>Planning</strong> <strong>with</strong> BD2A/BD2C3.4 Conductor cross sectionsCable entry plate single-core system for centre feeder units (undrilled cable entry plates)Type BD2.-400-ME... BD2.-1000-MECable entry plate BD2-400-MBAL BD2-1000-MBALNo. of cable entries (maximum) 12 x M40 and 3 x M32,6 x M50 and 4 x M4031 x M40,16 x M50 and 4 x M40Plastic cable glands <strong>with</strong> strain relief must be used (these are not included in the scope ofsupply).Cable entry plate feeder unit <strong>with</strong> switch disconnector (undrilled cable entry plates)Type BD2C-250(315, 400)-EESC BD2C-630(800)-EESCNo. of cable entries (maximum) 1 x 65.7 mm 2 x 65.7 mm<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong>68 <strong>Planning</strong> Manual, 10/2007, A5E01541101-01
<strong>Planning</strong> <strong>with</strong> BD2A/BD2C3.4 Conductor cross sections3.4.2 Tap-off unitsConductor cross sectionsNameTypeL1, L2, L3 N PE Size of fixingscrews, boltsL1, L2, L3minmm²maxmm²minmm²Up to 25 A BD2-AK1/S14 0.5 (f, m) 4 (e) 1 (e, f, m) 6 (e, m) 1 (e, f, m) 6 (e, m) –BD2-AK1/S18 0.5 (f, m) 16 (e, f, m) 1 (e, f, m) 6 (e, m) 1 (e, f, m) 6 (e, m) –BD2-AK1/A... 0.75 (e, m) 16 (e) 1 (e, f, m) 6 (e, m) 1 (e, f, m) 6 (e, m) –BD2-AK1/A...N 0.75 (e, m) 16 (e) 0.75 (e, m) 16 (e) 1 (e, f, m) 6 (e, m) –BD2-AK1/F... 0.75 (e, m) 16 (e) 1 (e, m) 6 (e) 1 (e, f, m) 6 (e, m) –BD2-AK1/F...N 0.75 (e, m) 16 (e) 0.75 (e, m) 16 (e) 1 (e, f, m) 6 (e, m) –Up to 63 A BD2-AK.2X/S18 0.5 (f, m) 25 (f, m) 1 (e, f, m) 6 (e, m) 1 (e, f, m) 6 (e, m) –BD2-AK.2X/S27 0.75 (f, m) 10 (e, f, m) 1 (e, f, m) 6 (e, m) 1 (e, f, m) 6 (e, m) –BD2-AK.2X/S33 1.5 (f, m) 25 (f, m) 2.5 (e, f, m) 16 (e, m) 2.5 (e, f, m) 16 (e, m) –BD2-AK.2M2/A... 0.75 (e, m) 25 (m) 2.5 (e, f, m) 25 (m) 2.5 (e, f, m) 25 (m) –BD2-AK.2M2/A...N 0.75 (e, m) 25 (m) 0.75 (e, f, m) 25 (m) 2.5 (e, f, m) 25 (m) –BD2-AK.2X/F... 0.75 (e, m) 25 (m) 2.5 (e, f, m) 25 (m) 2.5 (e, f, m) 25 (m) –BD2-0.75 (e, m) 16 (e, m) 0.75 (e, m) 16 (e, m) Armouring –AK.2X/GB32...BD2-0.75 (e, m) 50 (m) 0.75 (e, m) 50 (m) Armouring –AK.2X/GB63...Up to 125 A BD2-2.5 (e, m) 70 (m) 2.5 (e, m) 70 (m) 2.5 (e, m) 70 (m) –AK.3X/LSD40-LSD125BD2-AK3X/GS00 16 70 16 70 10 70 M8BD2-16 70 16 70 10 70 M8AK.3X/GSTZ(A)00BD2-6 (e, m) 70 (m) 6 (e, m) 70 (m) Armouring –AK.3X/GB100...BD2-6 (e, m) 70 (m) 6 (e, m) 70 (m) Armouring –AK03X/T(S)PNR100...Up to 250 A BD2-AK04/SNH1 6 150 6 150 6 150 M10BD2-AK04/FS... 6 150 6 150 6 150 M10BD2-AK04/LS... 6 120 (m) 6 (e, m) 150 6 150 M8Up to 400 A BD2-AK05/SNH2 10 2 × 120 10 2 × 120 10 2 × 120 M10BD2-AK05/FS... 10 2 × 120 10 2 × 120 10 2 × 120 M10BD2-AK05/LS... 10 2 × 120 10 2 × 120 10 2 × 120 M8Up to 630 A BD2-AK06/SNH3 10 2 × 240 10 2 × 240 10 2 × 240 M12BD2-AK06/LS... 10 2 × 240 10 2 × 240 10 2 × 240 M10e = solid, m = stranded, f = finely-stranded <strong>with</strong> end sleevemaxmm²minmm²maxmm²<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong><strong>Planning</strong> Manual, 10/2007, A5E01541101-01 69