<strong>Planning</strong> <strong>with</strong> BD2A/BD2C3.4 Conductor cross sectionsCable and wire entriesType BD2-AK1/... BD2-AK.2... BD2-AK.3... BD2-AK04 BD2-AK05 BD2-AK06Cable grommets M25 2) – – KT3 3) 2 × KT4 3) 2 × KT4 3)Cable glands 1) – M25, M32, M40 M25, M40, M63 – –for cable diameters mm 11 ... 16 11...27 11...42 14...54 14...68 14...68Min./max. insertable cable crosssections for NYY and NYCWY <strong>with</strong>multi-core cable for• NYY... mm 2 5 × 1.5 up to5 × 4• NYCWY... 4) mm 2 4 × 1.5 up to4 × 2.5Cable entry plate for single-corecable (add-on plates, undrilled)5 × 1.5 up to5 × 164 × 1.5 up to4 × 165 × 1.5 up to5 × 254 × 1.5 up to4 × 70– – –5 × 1.5 up to4 × 1502 × 5 × 1.5 up to2 × 4 × 150No. of cable entries, max. – – – 10 × M40 10 × M32,5 × M401) For cable glands: Plastic cable glands <strong>with</strong> strain relief must be used (these are not included in the scope of supply).2) Strain relief in the BD2-AK1/...3) With strain relief4) Fifth conductor: concentric conductor.2 × 5 × 10 up to2 × 4 × 24010 × M40<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong>70 <strong>Planning</strong> Manual, 10/2007, A5E01541101-01