<strong>Planning</strong> <strong>with</strong> LRC6.2 System components6.2.10 Incoming cable connection unitIf power needs to be supplied to the busbar trunking system via cables, you should use anLRC....-KE incoming cable connection unit.Figure 6-6Incoming cable connection unitThe incoming cable connection units are designed for rated currents from 800 to 3200 A.Enclosure sizesDesign4-conductor5-conductorSizeX = 0.40 mZ = 0.30 mZ1 = 0.06 mX = 0.50 mZ = 0.30 mZ1 = 0.06 mTagsClearance Width TypeX1 = X2 = X3 = 0.10 mY = 0.06 mLRC01 to LRC03Y = 0.09 mLRC04Y = 0.11 mLRC05Y = 0.12 mLRC06Y = 0.16 mLRC07Y = 0.19 mLRC08Y = 0.21 mLRC09 to LRC29You can connect single-core or multi-core cables. You can connect cross sections up to300 mm 2 (bolted connection) directly to the incoming cable connection unit bars.The cable connections are moulded to the tags on site once the cables have beenconnected. A moulding cast and cast resin mix are included in the scope of supply for thispurpose.<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong>220 <strong>Planning</strong> Manual, 10/2007, A5E01541101-01