<strong>Planning</strong> <strong>with</strong> LXA/LXC5.2 System components5.2.10 Incoming cable connection unitIf power needs to be supplied to the busbar trunking system via cables, you should use anLXA(C)....-KE incoming cable connection unit.Figure 5-4Incoming cable connection unitThe incoming cable connection unit is designed for rated currents from 800 to 3200 A.Enclosure sizesDepending on the system, three sizes can be selected:Size 1:Size 2:Size 3:LX.01...-KE to LXC02...-KELX.03...-KE and LXC(A)05...-KELX.06...-KE and LXC07..-The maximum dimensions are 920 mm x 639 mm x 490 mm (W x H x D).You can connect single-core or multi-core cables. You can connect cross sections up to300 mm 2 (bolted connection) directly to the incoming cable connection unit bars.The sheet steel flange plates and the cable sleeves are included in the scope of supply ofthe standard product. Single-core cables are supplied <strong>with</strong> an undrilled aluminium plate forcable entry.<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong><strong>Planning</strong> Manual, 10/2007, A5E01541101-01 161