<strong>Planning</strong> <strong>with</strong> LXA/LXC5.2 System componentsSelection example:A rated current of 2500 A is calculated for a project. Aluminium conductors shall be used. A5-pole system has to be used. The cross section of the neutral conductor needs to be equalto the cross section of the phase conductor.The following type is obtained: LXA07515.2.3 System sizes and structureSizesSizes are dependent upon rated current and conductor material. In total, there are six sizes.Seven sizes are set up as single systems and two as double systems.Single systems comprise one enclosure <strong>with</strong> between 3 and 6 aluminium or copper bars.Double systems have between 6 and 12 bars in two enclosures.The precise number of bars is determined by the required conductor configuration.Sizes (H x W 1) ), single systemHeight H [mm]System137 LXA(C)01, LXA(C)02162 LXC03, LXA(C)04207 LXA(C)05287 LXA(C)06, LXA(C)07Sizes (H x W 1) ), double systemHeight H [mm]System439 LXA(C)08599 LXA(C)09, LXA101) Width is always 145 mm<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong>152 <strong>Planning</strong> Manual, 10/2007, A5E01541101-01