Further information about planning7.1 Dimensioning and selectionVoltage drop diagramsThe following diagrams illustrate the voltage drop on the BD2A/BD2C, LDA/LDC LXA/LXCand LRC systems● taking into account the final heating resistances (in accordance <strong>with</strong> EN 60439-2)● <strong>with</strong> a load distribution factor– k = 1 for LDA/LDC, LXA/LXC and LRC– k = 0.5 for BD2A/BD2C● at rated current load. (In the case of a different current diversity factor, the value of thecurve must be multiplied by the appropriate distribution factor.)For systems <strong>with</strong> unevenly distributed loads, we recommend the SIMARIS design programfor calculating short circuits and load flows (see Tools and services). Voltage drop BD2AVoltage drop BD2C<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong>234 <strong>Planning</strong> Manual, 10/2007, A5E01541101-01