Further information about planning7.4 Fireproof barrierSystem a [cm] b [cm]LXA06../LXC06.. 35 49LXA07../LXC07.. 35 49LXA08../LXC08.. 35 64LXA09../LXC09.., LXA10.. 35 80LRC01.. - LRC03.. 19 19LRC04.. 22 22LRC05.., LRC06.. 22 25LRC07.. 22 29LRC08.. 22 32LRC09.. 22 34LRC27.. 22 48LRC28.. 22 54LRC29.. 22 58NoteThe area between the busbar wall and the wall cut-out must be filled <strong>with</strong> mortar or fireproofmaterial; these must meet applicable requirements <strong>with</strong> regard to the achievement of fireresistance class S90/S120.NoteMinimum clearanceFor the installation of <strong>SIVACON</strong> 8<strong>PS</strong> busbar systems <strong>with</strong> fire protection, a minimumclearance of 5 cm must be maintained between the system/system fire protection and thestructure in the cut-out. This ensures that there is sufficient space to mount the run, the fixingbrackets and for filling <strong>with</strong> mortar.<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong><strong>Planning</strong> Manual, 10/2007, A5E01541101-01 251