<strong>Planning</strong> <strong>with</strong> BD2A/BD2C3.2 System components3.2.8.3 Tap-off units up to 125 ATap-off units up to 125 A, <strong>with</strong> cover integrated load disconnectorSpecial features● With fuse base and fuse switch disconnector● Sheet-steel enclosure, hot-dip galvanised and cover <strong>with</strong> powdered paint finish, light greyin colour, RAL 7035● Anti-rotation feature prevents incorrect mounting.● Cover interlock for circuit-breaker and fuse switch disconnector● Multi-core cables can be fed in from three sides via knockouts● See technical data for conductor cross sections.NoteIf you are using fuse bases, you must disconnect the load prior to removing the enclosurecover.Figure 3-13Tap-off units up to 125 A, <strong>with</strong> cover integrated load disconnectorIe UeDesignTypeA V125 690 3-pole LV HRC fuse base size 00 BD2-AK3X/GS00125 690 3-pole LV HRC fuse switch disconnector size 00 BD2-AK3X/GSTZ00<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong>52 <strong>Planning</strong> Manual, 10/2007, A5E01541101-01