<strong>Planning</strong> <strong>with</strong> LXA/LXC5.3 Technical data5.3 Technical data5.3.1 LX trunking unitsStandards and regulations DIN EN 60439-1/VDE 0660-500DIN EN 60439-2/VDE 0660-502Resistance to extreme climates Damp heat, constant, acc. to IEC 60068-2-78 Damp heat, cyclic, acc. to IEC 60068-2-30Ambient temperature °C –5/+40/+35 (min./max./24-hour average)Torque for joint blockNm 120 ± 10(re-use)Busbar surface treatmentCoated <strong>with</strong> insulating material, aluminium also nickel-plated and tinnedTrunking unit materialPainted aluminium casingColour of trunking unitsRAL 7035 (light grey)Dimensions➜ Dimension drawings sectionRated insulation voltage Uiof the trunking units acc. to DIN EN 60439-1 V~V~Overvoltage category/pollution degreeRated operating voltage Ueof the trunking unitsV~ 690Rated frequency Hz 5010001000III/3 acc. to EN 60947<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong><strong>Planning</strong> Manual, 10/2007, A5E01541101-01 169