<strong>Planning</strong> <strong>with</strong> LRC6.3 Technical data6.3 Technical data6.3.1 General data for LRCStandards and regulations DIN EN 60439-1 and -2Rated insulation voltage Ui [V] AC/DC 1000Overvoltage category/pollution degreeRated operating voltage Ue [V] AC 1000Frequency [Hz] 50 ... 60Rated operating current630 ... 6300(copper bars A) Ie [A)Resistance to extreme climatesDamp heat (constant),to IEC 60068-2-78Damp heat (cyclic),to IEC 60068-2-30Ambient temperature [°C] * -5 ...+40Degree of protection acc. to IEC/EN 60529 (type 2)Busbar elementsIP68Connection elements/tap-off unitsIP68MaterialBusbar elements, connection elementsCopper (Cu), epoxy resinBusbarsLRCMounting positionEdgewise, flat, sidewaysColour Stone grey, similar to RAL 7030* Please ask about dimensioning for lower ambient temperaturesIII/3<strong>Planning</strong> <strong>with</strong> <strong>SIVACON</strong> 8 <strong>PS</strong>224 <strong>Planning</strong> Manual, 10/2007, A5E01541101-01