The mechanical effects of short-circuit currents in - Montefiore
The mechanical effects of short-circuit currents in - Montefiore
The mechanical effects of short-circuit currents in - Montefiore
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
V σ<br />
3<br />
2,5<br />
2<br />
1,5<br />
1<br />
<strong>mechanical</strong> resonance <strong>of</strong> the conductor with<br />
2f<br />
f<br />
17<br />
L1<br />
L2<br />
L3<br />
RX / = 0,07<br />
Λ = 0<br />
Λ = 0,2<br />
0,5<br />
0<br />
0,02<br />
HV-arrangements<br />
0,05 0,1 0,2 0,5<br />
( f )<br />
1<br />
( 2 f )<br />
2<br />
usual MV- and<br />
LV-arrangements<br />
5 10<br />
fc f /<br />
calculated<br />
standardized curve<br />
Figure 2.2 Calculated factors Vσ <strong>in</strong> the outer conductors L1 and L3 <strong>in</strong> the case <strong>of</strong> a three-phase <strong>short</strong> <strong>circuit</strong> as function <strong>of</strong> the related relevant<br />
natural frequency fc/f <strong>of</strong> the conductor and the logarithmic damp<strong>in</strong>g Λ, both ends fixed [Ref 8, Ref 9, Ref 19]. Also the standardised<br />
curve is given<br />
In Figure 2.2, R/X is 0,07, resp. κ = 1,81. When κ<br />
decreases, the maxima <strong>of</strong> the electromagnetic forces <strong>in</strong><br />
equations (2.15), (2.16), (2.18) decrease proportional to<br />
κ 2 , the decay<strong>in</strong>g and the frequent term decrease too,<br />
whereas the constant and the double frequent term are<br />
<strong>in</strong>dependent. That means Vσ <strong>in</strong>creases. <strong>The</strong> curves <strong>in</strong><br />
Figure 2.2 move to higher values while the standardised<br />
curve follows the m<strong>in</strong>ima. In the case <strong>of</strong> R/X ≤ 0,15<br />
resp. κ ≥ 1,64 the results are not very different.<br />
Sub-conductors are treated as beams with both ends<br />
fixed. <strong>The</strong>y act as ma<strong>in</strong> conductors but with other<br />
frequencies. To calculate the stress <strong>in</strong> the subconductors,<br />
the factor Vσs is set to unity (= 1) without<br />
consideration <strong>of</strong> the relevant natural frequency fcs. With<br />
consideration <strong>of</strong> the relevant natural frequency fcs the<br />
same figures can be used as for Vσ, but fc is to be<br />
replaced by fcs.<br />
S<strong>in</strong>gle-phase systems are to be handled <strong>in</strong> the same way.<br />
2.2.3.3 Forces on the sub-structures<br />
<strong>The</strong> forces on the sub-structures <strong>of</strong> the conductors are<br />
also calculated from the static <strong>short</strong>-<strong>circuit</strong> load Fm [Ref<br />
1, Ref 4, Ref 8, Ref 9, Ref 19, Ref 20]:<br />
(2.30)<br />
F = V V αF<br />
d<br />
F<br />
VF considers the dynamic response and α the<br />
distribution on the sub-structures.<br />
Fd acts at the clamp on the top <strong>of</strong> the <strong>in</strong>sulator. If the<br />
supports assumed to be rigid, the moment along the<br />
<strong>in</strong>sulator is l<strong>in</strong>ear. Supports <strong>in</strong> LV- and MV-substations<br />
r<br />
m<br />
fulfil this. Supports <strong>in</strong> HV-arrangements have a lower<br />
stiffness and <strong>in</strong>fluence the oscillation <strong>of</strong> the system.<br />
Along sub-structures <strong>of</strong> 110-kV-, 220-kV- and 380-kVsubstations,<br />
the maximum dynamic moments are<br />
calculated by means <strong>of</strong> Transfer-Matrix-Method [Ref<br />
20, Ref 24]. Figure 2.3 shows the results for the<br />
arrangement with two spans, described <strong>in</strong> [Ref 1,<br />
Volume 2, Case 1]. <strong>The</strong> measured values are also drawn<br />
and show a good agreement. <strong>The</strong> dynamic moment is<br />
nearly l<strong>in</strong>ear. In addition, the moment is given which<br />
follows from a static load with the maximum value <strong>of</strong><br />
the electromagnetic force; it is l<strong>in</strong>ear. In both cases, the<br />
maxima <strong>of</strong> the moments and with this the maximum<br />
stresses occur <strong>in</strong> the bottom <strong>of</strong> the <strong>in</strong>sulators and steel<br />
support structures. This justifies to take Fd as an<br />
equivalent static force at the clamp which gives the<br />
same moments as the dynamic force.<br />
<strong>The</strong> stress at the bottom <strong>of</strong> the <strong>in</strong>sulator by Fd must not<br />
be higher than the m<strong>in</strong>imum fail<strong>in</strong>g load <strong>of</strong> the <strong>in</strong>sulator<br />
which is given as a force FI at the top <strong>of</strong> the <strong>in</strong>sulator.<br />
<strong>The</strong>refore the moments have to fulfil the follow<strong>in</strong>g<br />
equation<br />
F h +<br />
h ≤ F h<br />
( ) (2.31) d I c I I