<strong>The</strong> histograms below for the <strong>in</strong>stant <strong>of</strong> occurrence lead<strong>in</strong>g to maximum asymmetry on the most loaded phase (here central phases n°3 and 4), the histograms 1,0 0,8 0,6 0,4 0,2 0,0 -0,2 -0,4 -0,6 -0,8 -1,0 94 below show the relative variation <strong>of</strong> loads on the other phases. Separate phases D=d Separate phases D=2d 1 2 3 4 5 6 1,0 0,8 0,6 0,4 0,2 0,0 -0,2 -0,4 -0,6 -0,8 -1,0 1 2 3 4 5 6 n (1) ~2 ~2 n (2) < 1,1 < 1,1 Figure 5.27 Relative variation <strong>of</strong> response at the maximum asymmetry 1) "<strong>short</strong> <strong>circuit</strong>" hypotheses 2) <strong>short</strong> <strong>circuit</strong> and w<strong>in</strong>d comb<strong>in</strong>ed hypotheses
<strong>The</strong> w<strong>in</strong>d may act <strong>in</strong> the same direction as the electrodynamic loads. This is the case for phases 2, 4 and 6 <strong>in</strong> the above histograms. But for the other phases it acts <strong>in</strong> the oppos<strong>in</strong>g direction. With respect to the number <strong>of</strong> loaded elements, the cumulated risks on the various phases <strong>of</strong> the two busbars gives a mean number n per suite <strong>of</strong> loaded post <strong>in</strong>sulators <strong>of</strong> less than 1.1 <strong>in</strong> the case <strong>of</strong> comb<strong>in</strong>ed loads and <strong>of</strong> approximately 2 <strong>in</strong> the case <strong>of</strong> a simple electrodynamic hypothesis. 5.2.3.7.4. Structures with a s<strong>in</strong>gle busbar For certa<strong>in</strong> substations with only one busbar or for cross connections comprised <strong>of</strong> rigid bars, the analyses made <strong>in</strong> 5.2.3.7.2 for the fault on a s<strong>in</strong>gle busbar can be reused. 5.2.3.7.5. Influence <strong>of</strong> connectors Another factor reduces the number <strong>of</strong> post <strong>in</strong>sulators concerned, i.e., the distribution <strong>of</strong> loads between post <strong>in</strong>sulators accord<strong>in</strong>g to the type <strong>of</strong> connector. <strong>The</strong> types <strong>of</strong> connector must frequently <strong>in</strong>stalled are: a) successions <strong>of</strong> clamped - clamped and p<strong>in</strong>ned - p<strong>in</strong>ned connectors. In this case, half the post <strong>in</strong>sulators (n=2) are loaded (ρ=0.5). b) successions <strong>of</strong> clamped - clamped then slid<strong>in</strong>g, - slid<strong>in</strong>g then p<strong>in</strong>ned - p<strong>in</strong>ned connectors. In this case, two-thirds <strong>of</strong> the post <strong>in</strong>sulators (n=3) are loaded (ρ=0.67). c) clamped - p<strong>in</strong>ned fitt<strong>in</strong>gs which distribute loads uniformly, which means that all post <strong>in</strong>sulators located relatively far from the extremities along the path <strong>of</strong> maximum <strong>currents</strong> are loaded (ρ=1). We def<strong>in</strong>e ρ as: (5.24) ρ = 1 n = 2ou3 n= 2 ou 3 ∑ n= 1 Risk( F / F ) Risk( F / F ) 0 n R <strong>The</strong> set (Fn) corresponds to the loads on the post <strong>in</strong>sulators <strong>of</strong> the most loaded busbar (longitud<strong>in</strong>al variation <strong>of</strong> load), but limited <strong>in</strong> size to two or three elements def<strong>in</strong>ed <strong>in</strong> paragraphs a) and b). 5.2.3.7.6. Common mode faults A dist<strong>in</strong>ction must be made between a substation and a family <strong>of</strong> substations. In the case <strong>of</strong> one substation, there may be common mode faults such as those result<strong>in</strong>g from component manufacture or assembly. Example: On a given substation, it is very likely that many <strong>of</strong> the ceramic post <strong>in</strong>sulators come from the same production batch. This may give rise to statistically above-average or below-average strength. In <strong>short</strong>, for the analysis <strong>of</strong> a family <strong>of</strong> substations, the advantages <strong>of</strong> the probabilistic approach are clearly apparent. R 95 5.2.3.7.7. Conclusions For N sequences on a section <strong>of</strong> busbars, we thus take . ρ . post <strong>in</strong>sulators subject to maximum loads. n N 5.2.3.8 FAILURE RECURRENCE TIME 5.2.3.8.1. Risk at a substation For l<strong>in</strong>e fault <strong>The</strong> overall maximum risk at a substation is given by the expression: (5.25) R l n N Risk F L o P = νλη . . . P. . ρ. . ( ) F with ν : normal operat<strong>in</strong>g rate <strong>of</strong> fault elim<strong>in</strong>ation (close to 1). λ : number <strong>of</strong> faults on overhead l<strong>in</strong>es connected per km and per year, η : rate <strong>of</strong> high-amplitude polyphase faults (hence nonresistive), lP : cumulative length <strong>of</strong> the risk zone <strong>in</strong> km, n : number <strong>of</strong> loaded post <strong>in</strong>sulators per busbar suite, ρ : coefficient depend<strong>in</strong>g on the type <strong>of</strong> connector N : suite number, Example: For λ=20x10 -2 per km and per year, η=30%, l=6km, n =1,5 ρ=1, N=14 suites, Risk Fo R ( )= 10 FR -5 , there is thus a probability <strong>of</strong> substation failure <strong>of</strong> around 7.6 10 - 5 , correspond<strong>in</strong>g to a recurrence time <strong>of</strong> more than 13000 years for a safety factor <strong>of</strong> 0.7. For l<strong>in</strong>e fault <strong>in</strong> the event <strong>of</strong> failure <strong>The</strong> previous analysis is also applicable <strong>in</strong> the event <strong>of</strong> failure (<strong>circuit</strong> breakers or protection devices), though the elim<strong>in</strong>ation times may be different and the result<strong>in</strong>g loads <strong>in</strong>creased. It is important to determ<strong>in</strong>e the amplitude <strong>of</strong> loads amplification, <strong>in</strong> view <strong>of</strong> the remarks made <strong>in</strong> section 5.2.3.1.4 on the effect <strong>of</strong> saturation when the clearance time exceeds the <strong>mechanical</strong> reaction time. In (5.25), Fo is replaced by F1 and the failure rate: ν : (protection system and/or <strong>circuit</strong> breaker failure rate) is taken <strong>in</strong>to account. <strong>The</strong> <strong>in</strong>crease <strong>in</strong> risk is <strong>of</strong>ten low and the reduction <strong>in</strong> the failure rate means that this term can be ignored. For substation fault <strong>The</strong> maximum overall risk at a substation is given by the expression: R n N Risk F P o P = λη . . . ρ. . ( ) with F λ : annual frequency <strong>of</strong> faults <strong>in</strong> the substation, η : rate <strong>of</strong> high-amplitude non-resistive polyphase faults (for example, accidental earth<strong>in</strong>g with all available network power). R
- Page 1 and 2:
THE MECHANICAL EFFECTS OF SHORT-CIR
- Page 3 and 4:
3.7. Special problems .............
- Page 5 and 6:
1. INTRODUCTION 1.1. GENERAL PRESEN
- Page 7 and 8:
The pinch (first maximum) can be ve
- Page 9 and 10:
1.3.3.2 Supporting structures Simil
- Page 11 and 12:
This method allows to state the sho
- Page 13 and 14:
and becomes the static force in equ
- Page 15 and 16:
(2.26) M el-pl ⎡ y d/ 2 y = 2⎢
- Page 17 and 18:
V σ 3 2,5 2 1,5 1 mechanical reson
- Page 19 and 20:
V F 3 2,5 2 1,5 1 mechanical resona
- Page 21 and 22:
1. eigenmode 2. eigenmode 3. eigenm
- Page 23 and 24:
(2.43) U E max max = 1 2 1 = 2 l
- Page 25 and 26:
m (2.47) M = σm = Z mσ m dm 2 J w
- Page 27 and 28:
profiles in Figure 2.14 it follows
- Page 29 and 30:
(2.71) 2 tube tube 4 tube U ∂U
- Page 31 and 32:
2.3.2. Influence of two busbars a)
- Page 33 and 34:
Asymmetrical associated-phase layou
- Page 35 and 36:
d)Methods used IEC 60865 method : -
- Page 37 and 38:
Section 3.4 deals with the effects
- Page 39 and 40:
In Figure 3.5 to Figure 3.8, the ma
- Page 41 and 42:
Figure 3.17 Comparison calculated a
- Page 43 and 44: movement of the dropper (swing out
- Page 45 and 46: This value has to be compared with
- Page 47 and 48: EN 60865-1 [Ref 3] with the assumpt
- Page 49 and 50: a) b) c) 3 m 2 1 0 -1 δ m δ 1 Mov
- Page 51 and 52: Droppers with fixed upper ends Duri
- Page 53 and 54: Manuzio developed a simplified meth
- Page 55 and 56: From prior tests the stiffness valu
- Page 57 and 58: Force / kN Force / kN 100mm 200mm 4
- Page 59 and 60: 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 ESL F
- Page 61 and 62: 3.7. SPECIAL PROBLEMS 3.7.1. Auto-r
- Page 63 and 64: for the maximum outswing and the ma
- Page 65 and 66: Zug-/Druck-Kraft in kN Z eit in s F
- Page 67 and 68: The numerical resolution of these e
- Page 69 and 70: 4. GUIDELINES FOR DESIGN AND UPRATI
- Page 71 and 72: standards and tested under specifie
- Page 73 and 74: 5. PROBABILISTIC APPROACH TO SHORT-
- Page 75: f G f(L) Lt Ls 75 G(L) ∞ R = ∫
- Page 78 and 79: Only the lowest break values are im
- Page 80 and 81: 5.2.2. A global Approach For analyz
- Page 82 and 83: to multinode operation can compared
- Page 84 and 85: 5.2.3.1.7. Proposed Approach The st
- Page 86 and 87: The first case (Figure 5.14) corres
- Page 88 and 89: centers are normally balanced by ba
- Page 90 and 91: Remark: The risk integral (5.3) can
- Page 92 and 93: 1,0 0,8 0,6 0,4 0,2 0,0 -0,2 -0,4 -
- Page 96 and 97: 5.2.3.8.2. Reliability based design
- Page 98 and 99: power converter in a three phase br
- Page 100 and 101: The time functions of the currents
- Page 102 and 103: a) Determination of the linear mome
- Page 104 and 105: Figure 6.11 Coefficients mJs1 and m
- Page 106 and 107: 7. REFERENCES Ref 1. IEC TC 73/CIGR
- Page 108 and 109: Ref 42. Stein, N.; Miri, A.M.; Meye
- Page 110 and 111: Ref 80. Fiabilité des structures d
- Page 112 and 113: 8. ANNEX 8.1. THE EQUIVALENT STATIC
- Page 114 and 115: Figure 8.2 What is ESL in this case
- Page 116 and 117: As the eigenfrequency of the portal
- Page 118 and 119: Figure 8.9 Case 3 (third eigenfrequ
- Page 120 and 121: Both cases have the same 200-kV-arr
- Page 122 and 123: a) c) 5 +25 % 0 % 4 3 F c / F st 2
- Page 124 and 125: a) b) 24 kN 20 +25 % 0 % 2,0 m F c
- Page 126 and 127: Case *11 (EDF 1990) This is the 102
- Page 128 and 129: 8.4. INFLUENCE OF THE RECLOSURE The
- Page 130 and 131: ( ( δ ) ( δ ) ) T = Mg08 . b r .
- Page 132 and 133: IEC 60865 Calculations If the clear
- Page 134 and 135: 8.6.1.1 With calculation of the rel
- Page 136 and 137: f) Calculation of the stresses due
- Page 138 and 139: d) Determination of the forces at t
- Page 140 and 141: 8.7. ERRATA TO BROCHURE NO 105 In V