24.11.2012 Views

The mechanical effects of short-circuit currents in - Montefiore

The mechanical effects of short-circuit currents in - Montefiore

The mechanical effects of short-circuit currents in - Montefiore

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

3.3. THE DROPPER BEHAVIOUR<br />

3.3.1. Introduction<br />

Droppers are suspended conductors between the ma<strong>in</strong><br />

bus bars or switch-bays and apparatus, <strong>in</strong>sulator support<br />

or bush<strong>in</strong>g. <strong>The</strong>se are the typical situations B and E <strong>in</strong><br />

Figure 1.1. <strong>The</strong> dropper stress is generally very low <strong>in</strong><br />

<strong>in</strong>itial conditions, i.e. less than 1 N/mm 2 , but can be<br />

stretched dur<strong>in</strong>g <strong>short</strong>-<strong>circuit</strong> <strong>mechanical</strong> <strong>effects</strong>. Either<br />

due to ma<strong>in</strong> bus or switch-bay cable oscillations (<strong>in</strong><br />

such a case there is no need to have any current <strong>in</strong> it) or<br />

simply due to electrodynamic forces if the <strong>short</strong>-<strong>circuit</strong><br />

current is go<strong>in</strong>g through it or <strong>in</strong> comb<strong>in</strong>ation <strong>of</strong> both.<br />

In addition to stretch, droppers are also submitted to<br />

tensile force dur<strong>in</strong>g sw<strong>in</strong>g-out, drop force and p<strong>in</strong>ch<br />

effect; (<strong>in</strong> the case <strong>of</strong> bundle configuration only). Due to<br />

the very unleveled structure and very low tension <strong>in</strong> it,<br />

dropper behaviour is quite different from the ma<strong>in</strong> bus<br />

and correspond<strong>in</strong>g <strong>effects</strong> cannot be evaluated by actual<br />

IEC/EN 60865-1.<br />

Droppers, generally more than one per span, and very<br />

sensibly <strong>in</strong>fluences the ma<strong>in</strong> bus <strong>mechanical</strong> behaviour<br />

limit<strong>in</strong>g by, for example, the fall<strong>in</strong>g down <strong>effects</strong>. <strong>The</strong>ir<br />

position <strong>in</strong> the bus, moreover to practical electrical<br />

aspects for design, can be chosen to limit the <strong>short</strong><strong>circuit</strong><br />

<strong>effects</strong> <strong>in</strong> the ma<strong>in</strong> bus. But the consequence on<br />

the dropper and correspond<strong>in</strong>g loads applied at the<br />

bottom <strong>of</strong> the dropper on apparatus must be carefully<br />

evaluated.<br />

Figure 3.20 details all k<strong>in</strong>d <strong>of</strong> dropper <strong>effects</strong> used <strong>in</strong><br />

open-air substations and classifies six different<br />

configurations.<br />

dropper<br />

fixed upper ends flexible upper ends<br />

<strong>effects</strong><br />

between<br />

phases<br />

<strong>effects</strong><br />

between<br />

sub-conductors<br />

non<br />

stretched<br />

s<strong>in</strong>gle bundle s<strong>in</strong>gle bundle s<strong>in</strong>gle<br />

stretched<br />

bundle<br />

1 2 3 4 5 6<br />

Figure 3.20 Case study for dropper configuration<br />

With configurations 1 and 2 the current is always<br />

flow<strong>in</strong>g through the droppers. Configurations 3 to 5<br />

occur when <strong>short</strong>-<strong>circuit</strong> current is go<strong>in</strong>g through the<br />

droppers. When there is no current <strong>in</strong> the dropper, the<br />

dangerous situation is limited to configurations 5 and 6<br />

with stretched droppers.<br />

In this chapter all these configurations will be evaluated<br />

either by simplified, if possible, or advanced computation<br />

method, which can be used <strong>in</strong> all<br />

configurations. Experimental confrontations with<br />

advanced methods are given <strong>in</strong> section 3.3.3, with<br />

42<br />

simplified method accord<strong>in</strong>g to IEC/EN 60865-1 <strong>in</strong><br />

annex 8.3.<br />

<strong>The</strong> f<strong>in</strong>al result will be to obta<strong>in</strong> the forces Ft and Ff <strong>in</strong><br />

the bus dur<strong>in</strong>g sw<strong>in</strong>g-out and fall <strong>of</strong> the bus and its<br />

maximum horizontal displacement as well as the load<br />

Fds <strong>in</strong> the lower clamp <strong>of</strong> the dropper and its<br />

correspond<strong>in</strong>g ESL.<br />

3.3.2. Typical oscillograms<br />

a) Droppers with fixed upper ends (configurations 1 and<br />

2)<br />

A dropper can have a fixed upper end as connection E<br />

<strong>in</strong> Figure 1.1. When connection B is fastened near the<br />

<strong>in</strong>sulator str<strong>in</strong>g, the upper end will move slightly due to<br />

the movement <strong>of</strong> the span and can be treated as (nearly)<br />

fixed. Both correspond to configurations 1 and 2 <strong>in</strong><br />

Figure 3.20.<br />

In configurations *17 for s<strong>in</strong>gle conductors and *18 for<br />

bundled conductors, oscillograms for droppers with<br />

fixed upper ends are given. Figure 3.21 shows an<br />

example.<br />

Figure 3.21 Oscillograms <strong>of</strong> horizontal components x and y <strong>of</strong> the<br />

load applied to support<strong>in</strong>g <strong>in</strong>sulator at the bottom side.<br />

Case *17, p. 79, Figure 17.2<br />

<strong>The</strong> droppers have no stretch<strong>in</strong>g because the two end<br />

po<strong>in</strong>ts are more or less fixed. Generally the<br />

electrodynamic load can be directly seen on the force. If<br />

the dropper length permits large movement, same<br />

behaviour as a ma<strong>in</strong> bus can be seen, sw<strong>in</strong>g out and<br />

fall<strong>in</strong>g down can occur, but the force value is much<br />

lower due to <strong>in</strong>itial very limited value. Some local<br />

<strong>effects</strong> i.e. right angle at the top can <strong>in</strong>duce some peaks<br />

just after <strong>short</strong>-<strong>circuit</strong> <strong>in</strong>ception.<br />

<strong>The</strong> test configuration can considerably affect the<br />

results. Especially for voltage level around 123 kV; that<br />

is because basic frequency <strong>of</strong> apparatus are close to 50<br />

or 60 Hz. This is true for test configurations *17 and<br />

*18.<br />

Bend<strong>in</strong>g stiffness <strong>of</strong> the conductors usually ignored has<br />

also significant <strong>in</strong>fluence on the loads applied at the<br />

fixation on the <strong>in</strong>sulator at the bottom. <strong>The</strong> clamp on the<br />

top <strong>of</strong> <strong>in</strong>sulator support was very rigid so that general

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!