The mechanical effects of short-circuit currents in - Montefiore
The mechanical effects of short-circuit currents in - Montefiore
The mechanical effects of short-circuit currents in - Montefiore
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
these cases, very low compared to that <strong>of</strong> phase 1,<br />
loaded at maximum asymmetry <strong>in</strong> a w<strong>in</strong>d act<strong>in</strong>g<br />
positively with respect to the <strong>short</strong>-<strong>circuit</strong> loads. For<br />
the phase to phase fault, the post <strong>in</strong>sulators are not<br />
excited to a maximum level, the risk is reduced by<br />
10% (0.9 equivalent "loaded post <strong>in</strong>sulator"). For the<br />
<strong>short</strong> <strong>circuit</strong> hypotheses, there are almost two loaded<br />
post <strong>in</strong>sulators.<br />
Three-phase fault on two busbars<br />
<strong>The</strong> diagram below shows the relative variation <strong>in</strong> the<br />
amplitudes <strong>of</strong> dynamic responses when the phase ϕ is<br />
varied on the 6 bars <strong>of</strong> a switch bay.<br />
1,0<br />
0,5<br />
0,0<br />
-0,5<br />
-1,0<br />
93<br />
1<br />
0,8<br />
0,6<br />
0,4<br />
0,2<br />
0<br />
0 30 60 90 120 150 180<br />
-0,2<br />
-0,4<br />
-0,6<br />
-0,8<br />
-1<br />
Figure 5.24 Relative variation <strong>of</strong> the response versus <strong>in</strong>stant <strong>of</strong><br />
occurrence <strong>of</strong> fault and busbars<br />
<strong>The</strong> ratio d/D is only relevant for faults concern<strong>in</strong>g<br />
two busbars. On the histograms below we note that<br />
the amplitude <strong>of</strong> loads is smaller compared to the<br />
three-phase fault on a s<strong>in</strong>gle busbar (reference 1).<br />
Three-phase fault on two busbars D=d three-phase fault on two busbars D=2d<br />
1 2 3 4 5 6<br />
1,0<br />
0,5<br />
0,0<br />
-0,5<br />
-1,0<br />
1 2 3 4 5 6<br />
n (1) ~1 ~1<br />
n (2) 0,5 0,5<br />
Figure 5.25 Relative variation <strong>of</strong> response at the maximum asymmetry<br />
1) "<strong>short</strong> <strong>circuit</strong>" hypotheses<br />
2) <strong>short</strong> <strong>circuit</strong> and w<strong>in</strong>d comb<strong>in</strong>ed hypotheses<br />
In terms <strong>of</strong> loaded elements, the faults on two busbars<br />
are substantially less stress-generat<strong>in</strong>g. <strong>The</strong> ma<strong>in</strong><br />
contribution is due to the outer post <strong>in</strong>sulators 1 and<br />
6. <strong>The</strong> ratio d/D has only a m<strong>in</strong>or <strong>in</strong>fluence.<br />
5.2.3.7.3. "Separate phases" layout<br />
For this type <strong>of</strong> arrangement (Figure 2.21), the stressgenerat<strong>in</strong>g<br />
fault is the three-phase fault on two<br />
busbars. <strong>The</strong> diagram below shows the relative<br />
variation <strong>in</strong> amplitudes <strong>of</strong> dynamic responses when<br />
the phase ϕ is varied on the 6 bars <strong>of</strong> a switch bay.<br />
1<br />
0,8<br />
0,6<br />
0,4<br />
0,2<br />
0<br />
-0,4<br />
-0,6<br />
-0,8<br />
-1<br />
Bar 1<br />
Bar 2<br />
Bar 3<br />
Bar 4<br />
Bar 5<br />
Bar 6<br />
0 30 60 90 120 150 180<br />
-0,2<br />
Figure 5.26 Relative variation <strong>of</strong> the response versus <strong>in</strong>stant <strong>of</strong><br />
occurrence <strong>of</strong> fault and busbars<br />
Bar 1<br />
Bar 2<br />
Bar 3<br />
Bar 4<br />
Bar 5<br />
Bar 6