24.11.2012 Views

The mechanical effects of short-circuit currents in - Montefiore

The mechanical effects of short-circuit currents in - Montefiore

The mechanical effects of short-circuit currents in - Montefiore

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

to mult<strong>in</strong>ode operation can compared with risk <strong>of</strong><br />

another drawback, <strong>mechanical</strong> failure.<br />

5.2.3.1.2. Instant <strong>of</strong> Occurrence <strong>of</strong> Faults<br />

<strong>The</strong> <strong>in</strong>stants <strong>of</strong> occurrence <strong>of</strong> faults (Figure 5.9 and<br />

Figure 5.10) were analyzed on the basis <strong>of</strong> 129<br />

record<strong>in</strong>gs made on RTE's 400-kV network us<strong>in</strong>g five<br />

digital fault recorders over a period last<strong>in</strong>g from 1981<br />

to 1984.<br />

Phase to earth fault<br />

<strong>The</strong> angle ϕ is def<strong>in</strong>ed by the phase angle difference<br />

between the ris<strong>in</strong>g voltage zero and the <strong>in</strong>stant <strong>of</strong><br />

occurrence <strong>of</strong> the fault.<br />

U = U t +<br />

(5.7) ( )<br />

0 2s<strong>in</strong>ω ϕ<br />

Figure 5.9 Histogram <strong>of</strong> angle ϕ distribution for a phase to<br />

earth fault. Frequency <strong>in</strong> %<br />

We note that the events are not equally likely. <strong>The</strong>re<br />

is a preference for positive alternation over negative<br />

alternation, which is due to the <strong>short</strong> <strong>circuit</strong>s<br />

produced by lightn<strong>in</strong>g and w<strong>in</strong>d and expla<strong>in</strong>ed by the<br />

preferentially negative ionization <strong>of</strong> air. It also<br />

appears that the maximum asymmetry ϕ =0 is not the<br />

most likely event. In other words, the phase<br />

distribution may differ significantly from uniform<br />

distribution.<br />

Phase To phase faults<br />

<strong>The</strong> phase to phase fault <strong>in</strong>cidence angle is def<strong>in</strong>ed by<br />

the phase angle difference relative to the zero po<strong>in</strong>t <strong>of</strong><br />

the phase-to-phase voltage.<br />

82<br />

Figure 5.10 Histogram <strong>of</strong> angle ϕ occurrence <strong>of</strong> phase to phase<br />

faults. Frequency <strong>in</strong> %<br />

We note that the frequencies <strong>of</strong> fault occurrence reach<br />

their maximum when ϕ approaches 90° or 270°, i.e.<br />

when the phase-to-phase voltage is maximum, with a<br />

preference for positive alternation.<br />

Three-Phase Faults<br />

For these more <strong>in</strong>frequent faults, establish<strong>in</strong>g<br />

statistics with the available data proved impossible.<br />

Proposed choice <strong>of</strong> an <strong>in</strong>stant <strong>of</strong> occurrence<br />

distribution<br />

Uniform distribution tends to raise the likelihood <strong>of</strong><br />

maximum asymmetry, thereby <strong>in</strong>creas<strong>in</strong>g the<br />

maximum stresses, which is still conservative. Hence,<br />

to simplify calculations, we propose a uniform<br />

distribution for all faults (Figure 5.18).<br />

5.2.3.1.3. Time Constant<br />

<strong>The</strong> time constantτ <strong>of</strong> the network varies depend<strong>in</strong>g<br />

on the type <strong>of</strong> fault (s<strong>in</strong>gle, two or three-phase) and<br />

its location. Frequently, the highest time constants<br />

arise from the transformer <strong>in</strong>puts, whereas the l<strong>in</strong>es<br />

have lower time constants. For a given substation, the<br />

result is a drop <strong>in</strong> the time constant as the distance<br />

between the fault and the substation <strong>in</strong>creases. <strong>The</strong><br />

usual choice <strong>of</strong> a standard value <strong>of</strong> 45 ms does not<br />

always cover the values encountered <strong>in</strong> networks. In<br />

other words, this parameter must be chosen with care.<br />

5.2.3.1.4. Clearance Time<br />

<strong>The</strong> clearance time may vary from one l<strong>in</strong>e to another<br />

for the same protection threshold, depend<strong>in</strong>g on the<br />

element on which the load is applied, the possibility<br />

<strong>of</strong> failure <strong>of</strong> a component such as the <strong>circuit</strong> breaker<br />

or the protection system. <strong>The</strong> Figure 5.11 shows the<br />

variation <strong>in</strong> clearance time for an extra high voltage<br />

l<strong>in</strong>e busbar connection <strong>in</strong> the RTE network.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!