15.10.2015 Views

SolarEdge

SolarEdge Installation Guide – MAN-01-00057-2.3

SolarEdge Installation Guide – MAN-01-00057-2.3

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Power Control Status<br />

Power Control Status<br />

Available from communication board (CPU) firmware version 2.7xx/3.7xx and later.<br />

P W R C T R L : R E M O T E<br />

P W R L i m i t : 1 0 . 0 4 k W<br />

C o s P h i : 0 . 9<br />

P o w e r P r o d : 7 0 0 0 W<br />

• PWR CTRL: The power control status:<br />

o REMOTE - Communication with the RRCR or smart energy manager is<br />

confirmed/validated.<br />

o<br />

LOCAL - The power is controlled locally (e.g. by a fixed limit), or this inverter<br />

limits the PV power production to its relative portion of the feed-in power limit,<br />

as a result of disconnected communication with the smart energy manager. If<br />

this status appears, check the communication to the smart energy manager or<br />

the communication to the meter.<br />

• PWR Limit: The inverter maximum output power set by one of the power limiting<br />

options:<br />

o RRCR<br />

o<br />

o<br />

o<br />

Smart energy manager (Feed-in limitation)<br />

P(f)<br />

Q(U)<br />

• Cos Phi: The ratio between active to reactive power<br />

• Power Prod: The power produced by the inverter<br />

For more information, refer to the following application notes:<br />

o<br />

o<br />

Power Control Application Note, available on the <strong>SolarEdge</strong> website at<br />

http://www.solaredge.com/files/pdfs/application_note_power_control_<br />

configuration.pdf<br />

Feed-in Limitation Application Note, available on the <strong>SolarEdge</strong> website at<br />

http://www.solaredge.com/files/pdfs/products/feed-in_limitation_application_<br />

note.pdf<br />

54<br />

<strong>SolarEdge</strong>-Installation Guide MAN-01-00057-3.1

Hooray! Your file is uploaded and ready to be published.