Creating an RS485 Bus Connection<br />
9. The inverter is configured by default to LAN. If reconfiguration is required:<br />
a. Make sure the ON/OFF switch is OFF.<br />
b. Turn ON the AC to the inverter by turning ON the circuit breaker on the main<br />
distribution panel.<br />
c. Use the internal user buttons to configure the connection, as described in<br />
Communication on page 43.<br />
NOTE<br />
If your network has a firewall, you may need to configure it to enable the<br />
connection to the following address:<br />
• Destination Address: prod.solaredge.com<br />
• TCP Port: 22222 (for incoming and outgoing data)<br />
10. Verify the connection, as described in Verifying the Connection on page 65.<br />
Creating an RS485 Bus Connection<br />
The RS485 option enables creating a bus of connected inverters, consisting of up to 31 slave<br />
inverters and 1 master inverter. Using this option, inverters are connected to each other in a<br />
bus (chain), via their RS485 connectors. The first and last inverters in the chain must be<br />
terminated.<br />
RS485 wiring specifications:<br />
• Cable type: Min. 3-wire shielded twisted pair (a 4-wire cable may be used)<br />
• Wire cross-section area: 0.2- 1 mm²/ 24-18 AWG (a CAT5 cable may be used)<br />
• Maximum nodes: 32<br />
• Maximum distance between first and last devices: 1 km /3300 ft.<br />
NOTE<br />
If using a cable longer than 10 m/33 ft in areas where there is a risk of induced voltage<br />
surges by lightning, it is recommend to use external surge protection devices. For details<br />
refer to: http://www.solaredge.com/files/pdfs/lightning_surge_protection.pdf. If<br />
grounded metal conduit are used for routing the communication wires, there is no need<br />
for a lightning protection device.<br />
NOTE<br />
If an electricity meter is connected to your inverter, it uses the RS485 port and therefore<br />
an RS485 communication bus cannot be created.<br />
The following sections describe how to physically connect the RS485 bus and how to configure<br />
the bus.<br />
60<br />
<strong>SolarEdge</strong>-Installation Guide MAN-01-00057-3.1