SE2200 SE3000 SE3500 SE4000 SE4000-16A SE5000 SE6000 Unit<br />
Output<br />
Rated AC power output 2200 3000 3500 4000 4000 5000 1 6000 W<br />
Maximum AC power output 2200 3000 3500 4000 4000 5000 1 6000 W<br />
AC output voltage (nominal) 220/230/240 Vac<br />
AC output voltage range 184 – 264.5 Vac<br />
AC frequency(nominal) 50/60 ±5 Hz<br />
Maximum continuous output current 12 16.5 2 19.5 2 22 16 27 27 A<br />
Max. continuous overcurrent<br />
protection<br />
12 16.5 2 19.5 2 22 16 27 27 A<br />
Residual current detector/ Residual<br />
current step detector<br />
300/30 mA<br />
Inrush current AC (Peak/Duration) 2.8/20<br />
Aac<br />
(rms)<br />
/ ms<br />
1 4985W when the country is set to Australia;4600W when the country is set to Germany or the Czech Republic.<br />
2 16A when the country is set to Denmark, Portugal, UK, or Poland. For other countries, contact <strong>SolarEdge</strong>.<br />