534 Barry’s Advanced Construction of Buildings<br />

Four-way locating gasket (will have<br />

metal anti-static strips where static<br />

may be a problem)<br />

Adjustable pedestal head<br />

Locking nut holds head at<br />

correct position<br />

Threaded mild steel tube<br />

Pedestal base plate either fixed<br />

using epoxy resin or other<br />

chemical adhesive or mechanically<br />

fixed using screws or bolts<br />

through predrilled holes in the<br />

base plate<br />

Pedestal base<br />

0.5–1 mm steel encased panel<br />

with 30 mm chipboard core<br />

Height adjustable up to 600 mm<br />

Figure 10.1 Raised floor pedestal.<br />

Suction lifting tools can<br />

be used to gain access<br />

to the void or replace<br />

panels<br />

Hot dip galvanised steel tray panel with highdensity<br />

particle board<br />

Wire cable trays and trunking help<br />

distribute electric and data cables<br />

below the floor<br />

Mineral-based fire<br />

barrier<br />

Specially design service panels can<br />

be used to accommodate outlets<br />

and inlets for heating, ventilation<br />

and air-conditioning units<br />

Pedestals set out on<br />

a 600 mm grid<br />

600 mm<br />

Concrete floor<br />

Figure 10.2 Raised floor.