Where to Locate Drive<br />
Consider the following:<br />
1. Locate the drive in an area consistent with<br />
the environment specifications listed in the<br />
Specifications section of this manual.<br />
Mount enclosures away from heavy and<br />
overhead construction.<br />
2. Select the type of enclosure that meets your<br />
application.<br />
Note: Standard AF93/IS903 NEMA 1 drives<br />
can withstand an ambient temperature of<br />
122¡F (50¡C) up to 3,300 feet (1000 meters)<br />
above sea level. Standard AF93/IS903<br />
NEMA 12 drives can withstand an ambient<br />
temperature of 104¡F (40¡C) up to 3,300 feet<br />
(1000 meters) above sea level. If you install<br />
the drive in an optional enclosure, the<br />
maximum temperature is derated.<br />
If you install an enclosure at temperatures<br />
exceeding these values, you must derate the<br />
unit as follows:<br />
For every 9¡F (5¡C) over the rated<br />
temperature you must derate the<br />
AF93/IS903 current ratings by 10%.<br />
However, do not exceed a maximum of<br />
131¡F (55¡C) under any circumstances.<br />
In addition for every 1000 feet (300 meters)<br />
above the rated altitude, you must derate the<br />
AF93/IS903 current ratings by 2%.<br />
Pre-Installation<br />
INSTALLATION<br />
3. Refer to the illustrations in the Drawings<br />
section of this manual for the mounting<br />
dimensions of each enclosure.<br />
4. Make sure there is plenty of ventilating<br />
space surrounding the drive. Refer to the<br />
illustrations in the Drawings section of this<br />
manual for ventilation clearances.<br />
AF93/IS903 Instruction Manual<br />
2-5