25.04.2013 Views

Cutler-Hammer - Eaton Canada

Cutler-Hammer - Eaton Canada

Cutler-Hammer - Eaton Canada

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

AF93/IS903 Parameter Descriptions<br />

USING THE PARAMETERS<br />

Remote Function (Cont.)<br />

ÒANALOG LOAD LIMÓ - This function combines<br />

a speed follower with an external method of<br />

controlling the load limit:<br />

Speed Follower - 4-20 mA connected to terminals<br />

1 and 2. A 0-5 VDC signal can also be connected<br />

to these terminals if the output impedance of the<br />

transducer is less than or equal to 250 ½ and it<br />

can output 20 mA.<br />

Load Limit Control - 0-10 VDC, connect it to<br />

terminals 2 and 3. Connect potentiometer to<br />

terminals 2, 3, and 4.<br />

This function allows you to control the load limit<br />

and speed from a remote station in situations<br />

where you expect wide variations in the load.<br />

Note that ÒANALOG LOAD LIMÓ is capped by<br />

ÒLOAD LIMITÓ (parameter 22).<br />

Remember, when the load limit you set is<br />

exceeded, the drive will go into foldback and<br />

reduce speed to try to prevent further overload.<br />

The lower you set the load limit, the lower the<br />

speed will be when the drive goes into foldback.<br />

If the load limit control does not prevent an<br />

overload, the drive will shut down.<br />

ÒDIGITAL POTÓ - This function sets up a<br />

ÒpotentiometerÓ that allows you to smoothly<br />

increase or decrease motor speed at a remote<br />

station.<br />

If you connect terminals 13 and 7, the speed<br />

increases at the rate established by Accel Time<br />

(parameter 11) or Accel Time 2 (parameter 14).<br />

When you disconnect terminal 13 from 7, the<br />

speed stops increasing and remains constant<br />

(drive ignores terminal 11, Jog).<br />

If you connect terminals 14 and 7, the speed<br />

decreases at the rate established by Decel Time<br />

(parameter 12) or Decel Time 2 (parameter 15).<br />

When you disconnect terminal 14 from 7, the<br />

speed stops decreasing and remains constant<br />

(drive ignores terminal 11, Jog).<br />

If both 13 and 14 are connected to 7 the speed<br />

decreases at a rate established by the<br />

appropriate deceleration time.<br />

AF93/IS903 Instruction Manual<br />

4-20<br />

The POT WPR (terminal 3) is used to set the<br />

load limit while in DIGITAL POT mode. If a load<br />

limit control potentiometer is not used to control<br />

torque, a jumper must be installed between<br />

terminals 3 and 4.<br />

Priority Interaction in REMOTE Mode<br />

There is a priority scheme that the drive uses to<br />

establish the speed setpoint in the REMOTE<br />

mode:<br />

Priority 1 (Lowest Priority) - 0-10 VDC Speed<br />

Follower<br />

Priority 2 - 4-20 mA Speed Follower (If Signal<br />

exceeds 1 mA)<br />

Priority 3 - PI Regulator<br />

Priority 4 - Terminals 12, 13, or 14 closed to<br />

terminal 7 (Preset Speeds or Digital<br />

Potentiometer)<br />

¥ If you use SPEED FOLLOWER, a current<br />

source greater than 1 mA will override a<br />

voltage source.<br />

¥ If you use SPEED FOLLOWER, a voltage<br />

source will override a current source less<br />

than 1 mA.<br />

¥ If you connect terminal 12, 13, or 14 to<br />

terminal 7, Preset Speeds will override<br />

SPEED FOLLOWER.<br />

¥ If you use PI REGULATOR, Preset Speeds<br />

will override the speed established by PI<br />

REGULATOR.<br />

¥ If you use ANALOG LOAD LIM, Preset<br />

Speeds will override the speed follower<br />

connected to terminals 1 and 2.<br />

¥ You cannot override speed set by DIGITAL<br />

POT, except by load limit.<br />

¥ The load limit you set (using parameter 22 or<br />

23) will fold back the speed setpoint when the<br />

load limit is exceeded.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!