Application Considerations<br />

Motor Selection<br />

Careful consideration of the proper motor is<br />

essential to obtain optimum performance from<br />

your drive. Contact your <strong>Cutler</strong>-<strong>Hammer</strong> sales<br />

representative or distributor for additional<br />

assistance and/or literature regarding motor<br />

selection and other aspects of drive applications.<br />

1. Your AF93/IS903 drive is designed to be<br />

connected directly to a single, NEMA design<br />

B, three phase AC motor. The motor must be<br />

selected and applied so that the average<br />

operating motor current and horsepower do<br />

not exceed the continuous current and<br />

horsepower ratings of the drive. The<br />

intermittent operating current must not<br />

exceed the intermittent current rating of the<br />

drive.<br />

2. Consider the effect of speed on the cooling<br />

capacity of the motor. As you slow down<br />

some types of motors (such as a Totally<br />

Enclosed Fan Cooled [TEFC]), its internal<br />

fan turns slower which reduces air flow<br />

through the motor. Typically, these types of<br />

motors may overheat if you operate them for<br />

extended periods of time at their rated<br />

torque and a reduced speed (less than 50%<br />

of full speed). Choose a motor that matches<br />

the expected duty, torque range and speed.<br />

Pre-Installation<br />

INSTALLATION<br />

3. Multiple motors may be operated by an<br />

AF93/IS903 drive if:<br />

¥ Total current from all motors does not<br />

exceed the current rating of the AF93/IS903.<br />

¥ Individual motor overload protection is<br />

supplied.<br />

¥ All motors must start and change speed<br />

together.<br />

! Warning<br />

If you configure the drive to operate above 60<br />

Hz, the motor may operate above its nameplate<br />

speed. Personal injury or equipment damage<br />

may exist when you operate the motor and<br />

driven machines above their rated speed. Make<br />

certain that all guards and shields are in place<br />

before operating at any speed. Refer to the<br />

motor manufacturer to verify safe motor speed.<br />