25.04.2013 Views

Cutler-Hammer - Eaton Canada

Cutler-Hammer - Eaton Canada

Cutler-Hammer - Eaton Canada

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Pre-Installation<br />

INSTALLATION<br />

Application Considerations<br />

When you plan your AF93/IS903 Adjustable<br />

Frequency Drive installation, consider its<br />

application. Different applications, such as<br />

industrial process control and HVAC system<br />

control, require different drive options, motors<br />

and software configuration.<br />

The following is a list of items you should keep in<br />

mind when you plan the installation and order<br />

the materials. It is important to note that some of<br />

the options available for your drive must be<br />

installed at the factory.<br />

AF93/IS903 Options<br />

1. Remember you must have an input line<br />

impedance of at least 1% and not over 5%<br />

for proper drive operation. You should<br />

calculate the input line impedance to<br />

determine whether a 1% input reactor is<br />

required. Refer to the discussion on Input<br />

Line Considerations later in this section for<br />

more details on determining input line<br />

impedance.<br />

2. Order a 3% or 5% input line reactor to<br />

correct input line harmonic distortions as<br />

required. Refer to the discussion on Input<br />

Line Characteristics on later in this section<br />

for more details for more details on harmonic<br />

distortions.<br />

AF93/IS903 Instruction Manual<br />

2-6<br />

3. An AF93/IS903 circuit breaker is a lockable<br />

means for disconnecting the motor from the<br />

power source. The circuit breaker is<br />

mounted in an optional NEMA 1 or 12<br />

enclosure or MCC.