25.04.2013 Views

Cutler-Hammer - Eaton Canada

Cutler-Hammer - Eaton Canada

Cutler-Hammer - Eaton Canada

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Solutions To Drive Problems<br />

TROUBLESHOOTING<br />

After you display the fault messages, you are ready to try to remedy<br />

the problems.<br />

An easy-to-use chart will help you quickly locate the possible causes<br />

to the problem. It also lists remedies you should try before you call for<br />

service.<br />

¥ The column labeled ÒMessageÓ lists all of the fault messages that<br />

can be displayed on the keypad.<br />

¥ The column labeled ÒPossible CausesÓ lists all of the things that<br />

might cause the message to appear. You will note that some of<br />

the possible causes are listed for more than one message. This<br />

can occur when a situation, such as a conveyor jamming, causes<br />

several situations, such as motor overload and inverter overload,<br />

to occur simultaneously.<br />

¥ The column labeled ÒSuggested RemediesÓ lists the things you<br />

can try before you call for service. Note that you cannot correct<br />

some of the situations yourself. In these cases, Òcall for serviceÓ is<br />

the only option listed.<br />

¥ If you exhaust all of the solutions and still get fault messages, call<br />

<strong>Cutler</strong>-<strong>Hammer</strong> for service.<br />

Refer to the Toll Free number on the back cover of this manual to<br />

speak to a <strong>Cutler</strong>-<strong>Hammer</strong> service representative.<br />

Running In Open Loop Test Mode<br />

You might want to run your drive without a motor connected during<br />

troubleshooting (this is called the OPEN LOOP TEST Mode):<br />

1. Apply power to the drive.<br />

2. Press the Operate button, (the Operate LCD is lights).<br />

3. Jumper terminal 7 to 8 and terminal 7 to 15.<br />

4. Press and hold the Operate button and press the Start button.<br />

5. Release both buttons.<br />

In the OPEN LOOP TEST Mode the keypad LCD displays the output<br />

voltage, speed, and frequency. Load and current values should be<br />

zero. Note that if you try to connect a motor to a drive in the OPEN<br />

LOOP TEST Mode, the drive will trip after 5 seconds and display<br />

ÒMotor Fault.Ó The drive will also trip on Motor Fault if you try to run<br />

with no motor connected in the default CLOSED LOOP Mode.<br />

To return to the default CLOSED LOOP Mode, press the Stop button.<br />

AF93/IS903 Instruction Manual<br />

5-3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!