AF93/IS903 Parameter Descriptions<br />
USING THE PARAMETERS<br />
Integral Gain<br />
Specifications<br />
Parameter Number: 24<br />
Mnemonic: INTEGRAL GAIN<br />
Range of Adjustment: 0 to 32,767<br />
Run Locked?: No<br />
Factory Setting: 0<br />
Refer to Remote Function (parameter 23), PI<br />
REGULATOR for application information.<br />
Proportional Gain<br />
Specifications<br />
Parameter Number: 25<br />
Mnemonic: PROPORTIONAL GN<br />
Range of Adjustment: 0 to 32,767<br />
Run Locked?: No<br />
Factory Setting: 0<br />
Refer to Remote Function (parameter 23), PI<br />
REGULATOR for application information.<br />
Preset Speeds 1 through 7<br />
Specifications<br />
Parameter Number: 26 to 32<br />
Mnemonic: PRESET SPEED x<br />
where ÒxÓ is a value of 1 to 7<br />
Range of Adjustment: Between Minimum Speed<br />
and Maximum Speed.<br />
Run Locked?: No<br />
Factory Setting: 0<br />
These parameters define speeds actuated by a<br />
remote signal. If the drive is in the KEYPAD<br />
mode, it will not respond to Preset Speed or Jog<br />
terminal block connections. If the drive is in<br />
REMOTE mode, Preset Speed terminal block<br />
connections override the 0-10 V or 4-20 mA<br />
speed follower. For a more complete explanation<br />
of the priority interaction, refer to Remote<br />
Function (parameter 23), Priority Interaction in<br />
REMOTE Mode.<br />
Note that if you use DIGITAL POT (Remote<br />
Function (parameter 23)), the drive ignores<br />
terminal 12 and Preset Speeds are not used to<br />
set the speed setpoint.<br />
Use the following chart to determine which of the<br />
seven Preset Speeds are in control. For<br />
example, if you connect terminals 12 and 7, the<br />
speed setpoint established by the<br />
PRESET SPEED 1 parameter will be used by the<br />
drive:<br />
Terminals Connected Preset Speed Set<br />
12 to 7 1<br />
13 to 7 2<br />
12 and 13 to 7 3<br />
14 to 7 4<br />
14 and 12 to 7 5<br />
14 and 13 to 7 6<br />
14 and 12 and 13 to 7 7<br />
Jog Speed<br />
Specifications<br />
Parameter Number: 33<br />
Mnemonic: JOG SPEED<br />
Range of Adjustment: Between Minimum Speed<br />
and Maximum Speed<br />
Run Locked?: No<br />
Factory Setting: 0<br />
The Jog function can only be activated via the<br />
terminal strip when the drive is in REMOTE<br />
mode. If the drive is at 0 speed or decelerating<br />
due to a Stop command, and Jog contact is<br />
closed (terminal 11 is connected to terminal 7)<br />
and run enable is closed (terminal 8 connected to<br />
terminal 7), the drive will start and go to the Jog<br />
Speed you set with this parameter. When the jog<br />
contact is opened, the drive will go back to<br />
previous speed command or next highest priority<br />
speed command.<br />
AF93/IS903 Instruction Manual<br />
4-21