Terminal Block<br />
The AF93/IS903 terminal block description is summarized in table 2-2 below:<br />
Terminal Name Terminal Description<br />
Specifications<br />
INSTALLATION<br />
1 LOOP Analog input speed reference from a 4-20mA current loop. Zin²250½. If SPEED FOLLOWER, PI REGULATOR, or ANALOG<br />
LOAD LIM (parameter 21) is enabled: Then if Iloop1 mA, terminal 3 is ignored and speed reference is taken from this input. Active in REMOTE mode only.<br />
2 AGND Analog signal common and shield tie point.<br />
3 POT WPR 0-10V Analog input speed command. May be attached to the wiper of a potentiometer or the output of a remote control circuit.<br />
Zin > 100 k½. Active if SPEED FOLLOWER, PI REGULATOR, or ANALOG LOAD LIM (parameter 23) is enabled.<br />
4 POT HI Analog input reference for external potentiometer. Requires a remote potentiometer of 1 k½ or greater.<br />
5 AOUT1 Programmable analog output 1. 0-10V signal represents 0 to full scale of the selected parameter.<br />
6 AOUT2 Programmable analog output 2. 0-10V signal represents 0 to full scale of the selected parameter.<br />
7 DIGCOM Digital Input Common. This is local digital ground.<br />
8 STOP Digital Input Stop/Run Enable Command. Must be LO (or connected to terminal 7) for drive to start or run; acts as a Run<br />
Enable. Momentary HI (or opening) stops the drive. Active in both KEYPAD and REMOTE modes. To run the drive in KEYPAD<br />
mode, a customer supplied jumper must be placed between terminals 7 and 8, and terminals 7 and 15. Attempting to start<br />
in KEYPAD mode without the jumper installation will yield a RUN DISABLED message. If drive is in AUTO RESTART mode, LO-<br />
HI (closed-open) transition exits the auto restart sequence and enters STOP mode without asserting a fault. If drive is in FAULT<br />
mode, LO- HI (closed-open) transition resets the fault and stops the drive.<br />
9 START Digital Start Input. In 3-wire control, a momentary contact between terminals 9 and 7 sends a RUN command to the drive. In<br />
2-wire control, a jumper is installed between terminals 9 and 7. Active when REMOTE mode is enabled. If drive is in AUTO<br />
RESTART mode, START is ignored. If drive is in FAULT mode, HI-LO (open-closed) transition while Run Enable is true resets<br />
the fault and starts the drive.<br />
10 FWD/REV Digital Fwd/Rev Input. HI (open) = Forward (clockwise rotation viewed from the motor shaft end); LO (closed to terminal 7)<br />
= Reverse (counter-clockwise rotation viewed from the motor shaft end). Active when REMOTE mode is enabled.<br />
11 ACC2/JOG Digital Accel/Decel2 Input / Jog Input. LO (closed to terminal 7) and RUN enable present (terminal 7 closed to terminal 8) selects<br />
second set of Accel/Decel presets in ACCEL2 mode; LO (closed to terminal 7) and RUN enable is present causes a jog motion in<br />
JOG mode. Active when REMOTE mode is selected.<br />
12 PRST1 Digital Preset Speed Input 1. Least Significant Bit (LSB) of a 3-bit binary coded speed preset select. HI (open) = 0 (OFF),<br />
LO (closed to terminal 7) =1 (ON). Active when REMOTE mode is selected.<br />
13 PRST2 Digital Preset Speed Input 2. Binary number selects one of seven internal presets entered from the setup menu. Code 0 (all<br />
inputs HI (open), OFF)) directs speed pot. or 4-20 mA current loop speed setting as command input. Active when REMOTE<br />
mode is selected.<br />
14 PRST3 Digital Preset Speed Input 3. MSB of a 3-bit binary coded speed preset select. Active when REMOTE mode is selected.<br />
15 EXTFLT Digital External Fault Trip Input. HI (opened to terminal 7) triggers an External Fault event and places the drive in FAULT mode,<br />
shutting it down. To run the drive in KEYPAD mode, customer supplied jumpers must be placed between terminals 7 and<br />
8 and terminals 7 and 15. Always active in both KEYPAD and REMOTE modes. Drive will coast to a stop.<br />
16 RLY1A Programmable Relay 1 NO contact<br />
17 RLY1B Programmable Relay 1 NO contact<br />
18 RLY2A Programmable Relay 2 NO contact<br />
19 RLY2B Programmable Relay 2 NO contact<br />
20 FLTNC Fault Relay NC contact<br />
21 FLTCOM Fault Relay Common<br />
22 FLTNO Fault Relay NO contact<br />
AF93/IS903 Terminal Block Descriptions<br />
Table 2-2<br />
AF93/IS903 Instruction Manual<br />
2-37