Solutions To Drive Problems<br />

TROUBLESHOOTING<br />

Message Possible<br />

Causes<br />

MOTOR FAULT<br />

HS OVER TEMP<br />

EXTERNAL FAULT<br />

MOTOR PARAM FAULT<br />

THERMAL OVERLOAD<br />

EE PROM FAIL<br />

SINGLE PHASE<br />

1. Excessive load on<br />

motor.<br />

2. Motor leads are open.<br />

Heat sink has exceeded<br />

198¡F (92¡C):<br />

1. Ambient temperature<br />

high.<br />

2. Blocked air flow.<br />

3. Fan not operating.<br />

4. Excessive load on<br />

motor.<br />

5. Impedance below 1%.<br />

1. External fault line<br />

has been opened.<br />

2. Inadequate resistors in<br />

optional Dynamic<br />

Brake package.<br />

Motor Related Parameter<br />

keypad entries are<br />

inconsistent. Example:<br />

Maximum Speed is lower<br />

than Minimum Speed.<br />

Indicates calculated<br />

motor temperature has<br />

exceeded rating<br />

EEPROM in drive circuit<br />

failed.<br />

Excessive load on single<br />

phase input<br />

Suggested<br />

Remedies<br />

1. Reduce load on motor.<br />

2. Check motor leads.<br />

1. Compare room air<br />

temperature to<br />

specifications.<br />

2. Check for blocked air<br />

flow.<br />

3. Check fan operation.<br />

4. Reduce load on motor.<br />

5. Install 1% line reactor.<br />

Reset external fault<br />

contact.<br />

Check the Motor Related<br />

Parameters. See Section 4,<br />

Using The Parameters, for<br />

the ranges of these<br />

parameters.<br />

Reduce load on motor.<br />

Replace drive, contact your<br />

<strong>Cutler</strong>-<strong>Hammer</strong> service<br />

representative.<br />

1. Check for high line<br />

voltage at each input<br />

phase is present (Drive<br />

terminals L1, L2, and L3).<br />

2. If this display occurs on<br />

a 240V AF93/IS903,<br />

please contact your<br />

<strong>Cutler</strong>-<strong>Hammer</strong> service<br />

representative.<br />

AF93/IS903 Instruction Manual<br />

5-5