C. Static-Dissipative Rubber Floor Tile: ASTM F 1344, except in manufacturer's standard hardness when tested per<br />

ASTM D 2240 using Shore, Type A durometer.<br />

1. Raised-Disc Tile: Class I-A (homogenous rubber, solid color); tiles 39.37 by 39.37 inches (1000 by 1000<br />

mm); 0.20-inch (5.0-mm) overall thickness, 0.19-inch (4.7-mm) base thickness.<br />

2. Hammered-Surface Textured Tile: Class I-B (homogenous rubber, through-mottled pattern).<br />

3. Smooth or Textured Surface Tile: Class I-B (homogenous rubber, through-mottled pattern).<br />

D. Static-Dissipative Vinyl Sheet Floor Covering: ASTM F 1913 (unbacked) or ASTM F 1303, Type II, Grade I, Class B<br />

(nonfoamed plastic backing); in manufacturer's standard roll size; in manufacturer's standard thickness, but not less<br />

than 0.08 inch (2.0 mm) thick.<br />

E. Static-Dissipative Rubber Sheet Floor Covering: ASTM F 1859, Type I (homogenous); in manufacturer's standard<br />

roll width and length; not less than 0.08 inch (2.0 mm).<br />

F. Static-Dissipative Recycled Rubber Sheet Floor Covering: Manufactured from post-consumer tire rubber; in<br />

manufacturer's standard roll width and length; 0.20 inch (5.0 mm) thick.<br />

G. Static-Control Properties:<br />

1. Electrical Resistance: Test per ASTM F 150 with 100-V applied voltage.<br />

a. Average greater than 1 megohm and less than or equal to 1000 megohms when test specimens are<br />

tested surface to ground.<br />

b. Average no less than 1 megohm and less than or equal to 1000 megohms when installed floor<br />

coverings are tested surface to ground.<br />

2. Static Generation: Less than 300 V when tested per AATCC-134 at 20 percent relative humidity with<br />

conductive footwear.<br />

3. Static Decay: 5000 to 0 V in less than 0.25 seconds when tested per FED-STD-101/4046.1.<br />

H. Color: As indicated in Appendix A.<br />

2.9 RESILIENT WALL BASE<br />

A. Wall Base: ASTM F 1861.<br />

B. Type (Material Requirement): As indicated in Appendix A.<br />

C. Group (Manufacturing Method): As indicated by product designation.<br />

D. Style, minimum thickness and height: As indicated in Appendix A.<br />

E. Lengths: Coils in manufacturer's standard length.<br />

F. <strong>Out</strong>side Corners: Job formed or premolded.<br />

G. Inside Corners: Job formed or premolded.<br />

H. Surface: Smooth.<br />

2.10 RESILIENT MOLDING ACCESSORY<br />

RESILIENT FLOORING 09 65 00 - 6