SINAMICS S120 drive system<br />

Line Modules and line-side components<br />

Smart Line Modules in chassis format<br />

© <strong>Siemens</strong> AG <strong>2013</strong><br />

3<br />

■ Technical specifications<br />

Smart Line Module in chassis format<br />

6SL3330-6T...<br />

Line connection voltage<br />

(up to 2000 m (6562 ft) above sea level)<br />

Line frequency<br />

Line power factor<br />

at rated output<br />

380 ... 480 V 3 AC ±10 % (in operation -15 % < 1 min) or<br />

500 ... 690 V 3 AC ±10 % (in operation -15 % < 1 min) 1)<br />

47 … 63 Hz<br />

• Fundamental power factor (cos ϕ 1 ) > 0.96<br />

•Total (λ) 0.75 … 0.93<br />

Overvoltage category<br />

Class III<br />

to EN 60664-1<br />

DC link voltage, approx. 2)<br />

1.32 × line voltage under partial load<br />

1.30 × line voltage under full load<br />

Main contactor control<br />

• Terminal strip X9/5-6<br />

240 V AC/max. 8 A<br />

30 V DC/max. 1A<br />

Radio interference suppression<br />

• Standard<br />

Category C3 to EN 61800-3 up to 300 m (984 ft) total cable length<br />

Type of cooling<br />

Forced air cooling by means of built-in fan<br />

Permissible ambient and coolant temperature (air)<br />

during operation for line-side components,<br />

Line Modules and Motor Modules<br />

Installation altitude<br />

Conformity<br />

Approvals, according to<br />

0 … 40 °C (32 … 104 °F) without derating,<br />

> 40 … 55 °C (104 …131 °F) see derating characteristics<br />

Up to 2000 m (6562 ft) above sea level without derating,<br />

> 2000 ... 4000 m (6562 ... 13124 ft) above sea level,<br />

see derating characteristics<br />

CE (Low Voltage and EMC Directives)<br />

cULus<br />

1) TT system with grounded external conductor is not permissible for line voltages > 600 V.<br />

2) The DC link voltage is unregulated and load-dependent.<br />