SINAMICS S120 drive system<br />

Line Modules and line-side components<br />

Basic Line Modules in booksize format<br />

© <strong>Siemens</strong> AG <strong>2013</strong><br />

■ Characteristic curves<br />

Overload capability<br />

Derating characteristics<br />

P<br />

G_D<strong>21</strong>1_EN_000182a<br />

3<br />

Pmax<br />

0.9 x<br />

P rated<br />

0.3 s<br />

10 s<br />

Load cycle with previous load<br />

P<br />

G_D<strong>21</strong>1_EN_000183a<br />

Permissible output current<br />

100<br />

%<br />

90<br />

80<br />

70<br />

G_D<strong>21</strong>2_EN_00058b<br />

60<br />

30 35 40 45 50 °C 55<br />

(86) (95) (104) (113) (122) (°F) (131)<br />

Ambient temperature<br />

2 x P<br />

rated<br />

Output power dependent on ambient temperature<br />

0.7 x<br />

P rated<br />

3 s<br />

Load cycle with previous load<br />

P<br />

Pmax<br />

PS6<br />

Prated<br />

0.4 x<br />

P rated<br />

4 min<br />

10 min<br />

20 s<br />

G_D<strong>21</strong>1_EN_00092a<br />

Permissible output current<br />

100<br />

%<br />

95<br />

90<br />

85<br />

80<br />

75<br />

70<br />

65<br />

60<br />

0 1000 2000 3000 m 4000<br />

(3281) (6562) (9843) (ft) (13124)<br />

Installation altitude above sea level<br />

Output power dependent on installation altitude<br />

G_D<strong>21</strong>2_EN_00060a<br />

S6 load cycle with previous load<br />

20 kW (26.8 HP) and 40 kW (53.6 HP) Basic Line Modules only<br />

2 x P<br />

P<br />

rated<br />

0.7 x<br />

P rated<br />

Load cycle with previous load<br />

10 s<br />

60 s<br />

G_D<strong>21</strong>1_EN_000184a<br />

Permissible input voltage in %<br />

of rated voltage<br />

100<br />

90<br />

80<br />

G_D<strong>21</strong>1_EN_00006b<br />

1.0<br />

0.9<br />

0.8<br />

70<br />

0.7<br />

0 1000 2000 3000 m 4000<br />

(3281) (6562) (9843) (ft) (13124)<br />

Installation altitude above sea level<br />

Derating factor k U<br />

Voltage derating dependent on installation altitude<br />

3/68 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>