SINAMICS S120 drive system<br />

Line Modules and line-side components<br />

Basic Line Modules in booksize format<br />

■ Technical specifications (continued)<br />

© <strong>Siemens</strong> AG <strong>2013</strong><br />

3<br />

Line voltage<br />

Basic Line Module in booksize format<br />

380 ... 480 V 3 AC<br />

• Internal air cooling 6SL3130-1TE22-0AA0 6SL3130-1TE24-0AA0 6SL3130-1TE31-0AA0<br />

• Cold plate cooling 6SL3136-1TE22-0AA0 6SL3136-1TE24-0AA0 6SL3136-1TE31-0AA0<br />

Power<br />

• Rated power P rated<br />

- At 380 V 3 AC<br />

- At 460 V 3 AC 2)<br />

kW<br />

(HP)<br />

20<br />

(25)<br />

40<br />

(50)<br />

100<br />

(125)<br />

• For S6 duty (40 %) P S6 kW 26 52 130<br />

• P max kW 60 120 175<br />

Braking power<br />

with external braking resistor<br />

• P Bmax. (= 2 × P rated ) kW 40 80 –<br />

• Continuous braking power P d<br />

kW 5 10 –<br />

(= 0.25 × P rated )<br />

DC link current<br />

• At 600 V DC A 34 67 167<br />

• For S6 duty (40 %) A 43 87 <strong>21</strong>7<br />

•Maximum A 100 200 292<br />

Input current<br />

• Rated current<br />

A 35 69 172<br />

at 380 V 3 AC<br />

•Maximum A 113 208 301<br />

Activation threshold<br />

V 774 774 –<br />

Braking chopper<br />

Resistance value<br />

Ω ≥ 14.8 ≥ 7.4 –<br />

of the external braking resistor<br />

Cable length, max.<br />

m (ft) 15 (50) 15 (50) –<br />

to braking resistor<br />

Connection for braking resistor (X2) Screw-type terminals Screw-type terminals –<br />

• Conductor cross-section, max. mm 2 0.5 … 4 0.5 … 10<br />

Current requirement, max.<br />

A 1 1.4 2<br />

24 V DC electronics power supply<br />

Current carrying capacity<br />

• 24 V DC busbars A 20 20 20<br />

• DC link busbars A 100 200 200<br />

DC link capacitance<br />

• Basic Line Module μF 940 1880 4100<br />

• Drive line-up, max. μF 20000 20000 50000<br />

Internal air cooling<br />

• Power loss 1) kW 0.144 0.284 0.628<br />

• Cooling air requirement m 3 /s (ft 3 /s) 0.016 (0.565) 0.031 (1.095) 0.05 (1.77)<br />

• Sound pressure level L pA (1 m) dB < 60 < 65 < 65<br />

Cold plate cooling<br />

• Power loss, int./ext. 1) kW 0.047/0.095 0.071/0.205 0.168/0.45<br />

• Thermal resistance R th K/W 0.075 0.05 0.045<br />

Line connection U1, V1, W1 Screw-type terminals Screw-type terminals M8 screw stud<br />

• Conductor cross-section, max. mm 2 0.5 … 16 10 … 50 1 × 35 … 120 or 2 × 50<br />

Shield connection Integrated into the power plug See Accessories See Accessories<br />

PE connection M5 screw M6 screw M6 screw<br />

Cable length, max.<br />

(total of all motor power cables and DC link)<br />

• Shielded/unshielded<br />

m (ft)<br />

1000/1500 (3281/49<strong>21</strong>)<br />

(above 630/850 m<br />

(2067/2789 ft) with Voltage<br />

Clamping Module)<br />

1000/1500 (3281/49<strong>21</strong>)<br />

(above 630/850 m<br />

(2067/2789 ft) with Voltage<br />

Clamping Module)<br />

Degree of protection IP20 IP20 IP20<br />

Dimensions<br />

• Width mm (in) 100 (3.94) 150 (5.91) 200 (7.87)<br />

•Height mm (in) 380 (15.0) 380 (15.0) 380 (15.0)<br />

•Depth<br />

- With internal air cooling mm (in) 270 (10.6) 270 (10.6) 270 (10.6)<br />

- With cold plate cooling mm (in) 226 (8.90) 226 (8.90) 226 (8.90)<br />

Weight, approx.<br />

- With internal air cooling kg (lb) 6.8 (15) 11.3 (25) 15.8 (35)<br />

- With cold plate cooling kg (lb) 6.4 (14) 10.9 (24) 16.4 (36)<br />

1000/1500 (3281/49<strong>21</strong>)<br />

(above 630/850 m<br />

(2067/2789 ft) with Voltage<br />

Clamping Module)<br />

1) Power loss of Basic Line Module at rated output including losses of 24 V DC electronics power supply.<br />

2) Nominal HP ratings are provided for ease of assigning components only. The Line Module outputs are dependent on the Motor Module loading and are to be<br />

dimensioned accordingly.<br />

3/66 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>