© <strong>Siemens</strong> AG <strong>2013</strong><br />

SINAMICS S120 drive system<br />

Power Modules and line-side components<br />

Air-cooled Power Modules<br />

in blocksize format<br />

■ Technical specifications (continued)<br />

Line voltage<br />

Air-cooled <strong>PM</strong>340 Power Module in blocksize format<br />

380 … 480 V 3 AC 6SL3<strong>21</strong>0-<br />

1SE23-8...<br />

6SL3<strong>21</strong>0-<br />

1SE24-5...<br />

6SL3<strong>21</strong>0-<br />

1SE26-0...<br />

6SL3<strong>21</strong>0-<br />

1SE27-5...<br />

6SL3<strong>21</strong>0-<br />

1SE31-0...<br />

Output current<br />

• Rated current I rated A 38 45 60 75 90<br />

• Base-load current I H A 33 40 48 65 80<br />

• For S6 duty (40 %) I S6 A 49 58 78 98 117<br />

• I max A 64 76 90 124 150<br />

Type rating 1)<br />

• Based on I rated kW (HP) 18.5 (25) 22 (30) 30 (40) 37 (50) 45 (60)<br />

• Based on I H kW (HP) 15 (20) 18.5 (30) 22 (30) 30 (50) 37 (60)<br />

Rated pulse frequency kHz 4 4 4 4 4<br />

Power loss kW 0.38 0.51 0.69 0.99 1.<strong>21</strong><br />

Cooling air requirement m 3 /s (ft 3 /s) 0.022 (0.8) 0.022 (0.8) 0.039 (1.4) 0.022 (0.8) 0.039 (1.4)<br />

Sound pressure level L pA dB < 60 < 60 < 61 < 60 62<br />

(1 m)<br />

24 V DC power supply A 1.0 1.0 1.0 1.0 1.0<br />

for the Control Unit<br />

Rated input current 2) A 40/46 47/53 63/72 78/88 94/105<br />

with/without line reactor<br />

Resistance value<br />

Ω ≥ 27 ≥ 27 ≥ 27 ≥ 15 ≥ 15<br />

of the external braking resistor<br />

Cable length<br />

m (ft) 15 (49) 15 (49) 15 (49) 15 (49) 15 (49)<br />

to braking resistor, max.<br />

Line connection<br />

M6 screw stud M6 screw stud M6 screw stud M6 screw stud M6 screw stud<br />

U1/L1, V1/L2, W1/L3<br />

• Conductor cross-section mm 2 10 … 35 10 … 35 10 … 35 10 … 35 10 … 35<br />

DC link connection,<br />

M6 screw stud M6 screw stud M6 screw stud M6 screw stud M6 screw stud<br />

connection for<br />

braking resistor<br />

DCP/R1, DCN, R2<br />

• Conductor cross-section mm 2 10 … 35 10 … 35 10 … 35 10 … 35 10 … 35<br />

Motor connection<br />

M6 screw stud M6 screw stud M6 screw stud M6 screw stud M6 screw stud<br />

U2, V2, W2<br />

• Conductor cross-section mm 2 10 … 35 10 … 35 10 … 35 10 … 35 10 … 35<br />

PE connection M6 screw M6 screw M6 screw M6 screw M6 screw<br />

Motor cable length 3) , max.<br />

• Shielded m (ft) 70 (230) 70 (230) 70 (230) 70 (230) 70 (230)<br />

• Unshielded m (ft) 100 (328) 100 (328) 100 (328) 100 (328) 100 (328)<br />

Degree of protection IP20 IP20 IP20 IP20 IP20<br />

Dimensions<br />

• Width mm (in) 275 (10.83) 275 (10.83) 275 (10.83) 275 (10.83) 275 (10.83)<br />

• Height <strong>PM</strong>340<br />

without/with int. filter<br />

mm (in) 418.3/511<br />

(16.5/20.1)<br />

418.3/511<br />

(16.5/20.1)<br />

418.3/511<br />

(16.5/20.1)<br />

498.3/633<br />

(19.6/24.9)<br />

498.3/633<br />

(19.6/24.9)<br />

•Depth<br />

-<strong>PM</strong>340 mm (in) 203.5 (8.01) 203.5 (8.01) 203.5 (8.01) 203.5 (8.01) 203.5 (8.01)<br />

- <strong>PM</strong>340 with CU310-2/D410-2 mm (in) 293.1 (11.5) 293.1 (11.5) 293.1 (11.5) 293.1 (11.5) 293.1 (11.5)<br />

- <strong>PM</strong>340 with CUA31/CUA32 mm (in) 233.8 (9.20) 233.8 (9.20) 233.8 (9.20) 233.8 (9.20) 233.8 (9.20)<br />

Frame size FSD FSD FSD FSE FSE<br />

Weight, approx.<br />

<strong>PM</strong>340 without/with int. filter<br />

kg (lb) 15.9/19.3 (35/43) 15.9/19.3 (35/43) 15.9/19.3 (35/43) 19.8/27.1 (44/60) 19.8/27.1 (44/60)<br />

3<br />

1) Nominal HP based on asynchronous (induction) motors and 460 V 3 AC. For specific sizing select drive based on motor nameplate current and overload.<br />

2) The input current depends on the motor load and line impedance.<br />

The input currents apply for rated power loading (based on I rated ) for a line impedance corresponding to u k = 1 %.<br />

3) Max. motor cable length 25 m (82 ft) (shielded) for <strong>PM</strong>340 Power Modules with integrated line filter to maintain the limit values of EN 61800-3 Category C2.<br />

<strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong><br />