© <strong>Siemens</strong> AG <strong>2013</strong><br />
SINAMICS S120 drive system<br />
Power Modules and line-side components<br />
Air-cooled Power Modules<br />
in blocksize format<br />
■ Technical specifications (continued)<br />
Line voltage<br />
Air-cooled <strong>PM</strong>340 Power Module in blocksize format<br />
380 … 480 V 3 AC 6SL3<strong>21</strong>0-<br />
1SE23-8...<br />
6SL3<strong>21</strong>0-<br />
1SE24-5...<br />
6SL3<strong>21</strong>0-<br />
1SE26-0...<br />
6SL3<strong>21</strong>0-<br />
1SE27-5...<br />
6SL3<strong>21</strong>0-<br />
1SE31-0...<br />
Output current<br />
• Rated current I rated A 38 45 60 75 90<br />
• Base-load current I H A 33 40 48 65 80<br />
• For S6 duty (40 %) I S6 A 49 58 78 98 117<br />
• I max A 64 76 90 124 150<br />
Type rating 1)<br />
• Based on I rated kW (HP) 18.5 (25) 22 (30) 30 (40) 37 (50) 45 (60)<br />
• Based on I H kW (HP) 15 (20) 18.5 (30) 22 (30) 30 (50) 37 (60)<br />
Rated pulse frequency kHz 4 4 4 4 4<br />
Power loss kW 0.38 0.51 0.69 0.99 1.<strong>21</strong><br />
Cooling air requirement m 3 /s (ft 3 /s) 0.022 (0.8) 0.022 (0.8) 0.039 (1.4) 0.022 (0.8) 0.039 (1.4)<br />
Sound pressure level L pA dB < 60 < 60 < 61 < 60 62<br />
(1 m)<br />
24 V DC power supply A 1.0 1.0 1.0 1.0 1.0<br />
for the Control Unit<br />
Rated input current 2) A 40/46 47/53 63/72 78/88 94/105<br />
with/without line reactor<br />
Resistance value<br />
Ω ≥ 27 ≥ 27 ≥ 27 ≥ 15 ≥ 15<br />
of the external braking resistor<br />
Cable length<br />
m (ft) 15 (49) 15 (49) 15 (49) 15 (49) 15 (49)<br />
to braking resistor, max.<br />
Line connection<br />
M6 screw stud M6 screw stud M6 screw stud M6 screw stud M6 screw stud<br />
U1/L1, V1/L2, W1/L3<br />
• Conductor cross-section mm 2 10 … 35 10 … 35 10 … 35 10 … 35 10 … 35<br />
DC link connection,<br />
M6 screw stud M6 screw stud M6 screw stud M6 screw stud M6 screw stud<br />
connection for<br />
braking resistor<br />
DCP/R1, DCN, R2<br />
• Conductor cross-section mm 2 10 … 35 10 … 35 10 … 35 10 … 35 10 … 35<br />
Motor connection<br />
M6 screw stud M6 screw stud M6 screw stud M6 screw stud M6 screw stud<br />
U2, V2, W2<br />
• Conductor cross-section mm 2 10 … 35 10 … 35 10 … 35 10 … 35 10 … 35<br />
PE connection M6 screw M6 screw M6 screw M6 screw M6 screw<br />
Motor cable length 3) , max.<br />
• Shielded m (ft) 70 (230) 70 (230) 70 (230) 70 (230) 70 (230)<br />
• Unshielded m (ft) 100 (328) 100 (328) 100 (328) 100 (328) 100 (328)<br />
Degree of protection IP20 IP20 IP20 IP20 IP20<br />
Dimensions<br />
• Width mm (in) 275 (10.83) 275 (10.83) 275 (10.83) 275 (10.83) 275 (10.83)<br />
• Height <strong>PM</strong>340<br />
without/with int. filter<br />
mm (in) 418.3/511<br />
(16.5/20.1)<br />
418.3/511<br />
(16.5/20.1)<br />
418.3/511<br />
(16.5/20.1)<br />
498.3/633<br />
(19.6/24.9)<br />
498.3/633<br />
(19.6/24.9)<br />
•Depth<br />
-<strong>PM</strong>340 mm (in) 203.5 (8.01) 203.5 (8.01) 203.5 (8.01) 203.5 (8.01) 203.5 (8.01)<br />
- <strong>PM</strong>340 with CU310-2/D410-2 mm (in) 293.1 (11.5) 293.1 (11.5) 293.1 (11.5) 293.1 (11.5) 293.1 (11.5)<br />
- <strong>PM</strong>340 with CUA31/CUA32 mm (in) 233.8 (9.20) 233.8 (9.20) 233.8 (9.20) 233.8 (9.20) 233.8 (9.20)<br />
Frame size FSD FSD FSD FSE FSE<br />
Weight, approx.<br />
<strong>PM</strong>340 without/with int. filter<br />
kg (lb) 15.9/19.3 (35/43) 15.9/19.3 (35/43) 15.9/19.3 (35/43) 19.8/27.1 (44/60) 19.8/27.1 (44/60)<br />
3<br />
1) Nominal HP based on asynchronous (induction) motors and 460 V 3 AC. For specific sizing select drive based on motor nameplate current and overload.<br />
2) The input current depends on the motor load and line impedance.<br />
The input currents apply for rated power loading (based on I rated ) for a line impedance corresponding to u k = 1 %.<br />
3) Max. motor cable length 25 m (82 ft) (shielded) for <strong>PM</strong>340 Power Modules with integrated line filter to maintain the limit values of EN 61800-3 Category C2.<br />
<strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong><br />
3/35