Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
© <strong>Siemens</strong> AG <strong>2013</strong><br />
SINAMICS S120 drive system<br />
Line Modules and line-side components<br />
Basic Line Modules in chassis format<br />
■ Technical specifications (continued)<br />
Line voltage<br />
500 ... 690 V 3 AC<br />
Basic Line Module in chassis format<br />
6SL3330-<br />
1TG33-0AA3<br />
6SL3330-<br />
1TG34-3AA3<br />
6SL3330-<br />
1TG36-8AA3<br />
6SL3330-<br />
1TG41-1AA3<br />
6SL3330-<br />
1TG41-4AA3<br />
Infeed power<br />
• Rated power P rated<br />
kW 250 355 560 900 1100<br />
at 690 V 3 AC 1)<br />
• At 500 V 3 AC kW 180 250 400 650 800<br />
• P max<br />
kW 375 532.5 840 1350 1650<br />
at 690 V 3 AC 1)<br />
DC link current<br />
• Rated current I rated_DC A 300 430 680 1100 1400<br />
• I H_DC A 234 335 530 858 1092<br />
• I max_DC A 450 645 1020 1650 <strong>21</strong>00<br />
Input current<br />
•At V line = 690 V A 260 375 575 925 1180<br />
•Maximum A 390 562.5 862.5 1387.5 1770<br />
Current requirement<br />
A 1.1 1.1 1.1 1.1 1.1<br />
24 V DC electronics<br />
power supply, max.<br />
DC link capacitance<br />
• Basic Line Module μF 3200 4800 7300 11600 15470<br />
• Drive line-up, max. μF 25600 38400 58400 92800 123760<br />
Power loss kW 1.5 2.1 3.0 5.4 5.8<br />
Cooling air requirement m 3 /s (ft 3 /s) 0.17 (6.00) 0.17 (6.00) 0.17 (6.00) 0.36 (12.7) 0.36 (12.7)<br />
Sound pressure level<br />
L pA (1 m) at 50/60 Hz<br />
dB 66/68 66/68 66/68 71/73 71/73<br />
Line connection<br />
U1, V1, W1<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M12 screw<br />
• Conductor cross-section, max. mm 2 2 × 240 2 × 240 2 × 240 6 × 185 6 × 185<br />
DC link connection<br />
DCP, DCN<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M10 screw<br />
Flat connector for<br />
M12 screw<br />
Flat connector for<br />
M12 screw<br />
Flat connector for<br />
M12 screw<br />
• Conductor cross-section, max. mm 2 2 × 240 2 × 240 2 × 240 6 × 185 6 × 185<br />
PE connection M10 screw M10 screw M10 screw M12 screw M12 screw<br />
• Conductor cross-section, max. mm 2 2 × 240 2 × 240 2 × 240 4 × 240 4 × 240<br />
Cable length, max.<br />
(total of all motor power cables<br />
and DC link)<br />
• Shielded m (ft) 1500 (49<strong>21</strong>) 1500 (49<strong>21</strong>) 1500 (49<strong>21</strong>) 2250 (7382) 2250 (7382)<br />
• Unshielded m (ft) 2250 (7382) 2250 (7382) 2250 (7382) 3375 (11073) 3375 (11073)<br />
Degree of protection IP00 IP00 IP00 IP00 IP00<br />
Dimensions<br />
• Width mm (in) 310 (12.2) 310 (12.2) 310 (12.2) 310 (12.2) 310 (12.2)<br />
•Height mm (in) 1164 (45.8) 1164 (45.8) 1164 (45.8) 1653 (65.1) 1653 (65.1)<br />
•Depth mm (in) 352 (13.9) 352 (13.9) 352 (13.9) 550 (<strong>21</strong>.6) 550 (<strong>21</strong>.6)<br />
Frame size FB FB FB GB GB<br />
Weight, approx. kg (lb) 96 (<strong>21</strong>2) 96 (<strong>21</strong>2) 96 (<strong>21</strong>2) <strong>21</strong>4 (472) <strong>21</strong>4 (472)<br />
3<br />
1) The infeed power is proportional to the line voltage. With 500 V 3 AC, the power is reduced by a factor of 690/500 = 1.38.<br />
<strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong><br />