SINAMICS S120 drive system<br />

Line Modules and line-side components<br />

Active Line Modules in chassis format<br />

© <strong>Siemens</strong> AG <strong>2013</strong><br />

3<br />

■ Selection and ordering data<br />

Rated power<br />

Active Line Module<br />

in chassis format<br />

kW (HP)<br />

Order No.<br />

Line voltage 380 ... 480 V 3 AC<br />

132 (200) 6SL3330-7TE32-1AA3<br />

160 (225) 6SL3330-7TE32-6AA3<br />

235 (350) 6SL3330-7TE33-8AA3<br />

300 (450) 6SL3330-7TE35-0AA3<br />

380 (550) 6SL3330-7TE36-1AA3<br />

450 (600) 6SL3330-7TE37-5AA3<br />

500 (700) 6SL3330-7TE38-4AA3<br />

630 (800) 6SL3330-7TE41-0AA3<br />

800 (1000) 6SL3330-7TE41-2AA3<br />

900 (1150) 6SL3330-7TE41-4AA3<br />

Line voltage 500 ... 690 V 3 AC<br />

560 6SL3330-7TG35-8AA3<br />

800 6SL3330-7TG37-4AA3<br />

1100 6SL3330-7TG41-0AA3<br />

1400 6SL3330-7TG41-3AA3<br />

Accessories<br />

Warning labels in 30 languages 6SL3166-3AB00-0AA0<br />

This set of foreign language warning<br />

signs can be placed on top of the<br />

standard English or German signs.<br />

A set of signs is supplied with the units.<br />

One sign in each of the following<br />

languages is provided in each set:<br />

BG, CN, CZ, DE, DK, EE, ES, FI, FR,<br />

GB, GR, HU, IE, IS, IT, JP, KR, LT, LV,<br />

MT, NL, NO, PL, PT, RO, RU, SE, SI,<br />

SK, TR<br />

SINAMICS/SINUMERIK/SIMOTION 6SL3066-4CA00-0AA0<br />

dust-proof blanking plugs<br />

(50 units)<br />

For DRIVE-CLiQ port<br />

■ Characteristic curves<br />

Overload capability<br />

G_D<strong>21</strong>1_EN_00036b<br />

max_DC<br />

1.5 x H_DC<br />

rated_DC<br />

H_DC<br />

High overload<br />

5 s<br />

60 s<br />

300 s<br />

■ Characteristic curves (continued)<br />

Derating characteristics<br />

Derating factor k T<br />

1.3<br />

1.2<br />

1.1<br />

1.0<br />

0.9<br />

Current derating dependent on ambient temperature<br />

Note: A derating factor k T > 1.0 is to be taken into account only<br />

in conjunction with "current derating dependent on installation<br />

altitude".<br />

See also chapter System description – Dimensioning.<br />

Permissible continuous current in %<br />

of rated current<br />

Current derating dependent on installation altitude<br />

Permissible input voltage in %<br />

of rated voltage<br />

G_D<strong>21</strong>1_EN_00004c<br />

0.8<br />

20 25 30 35 40 45 50 °C 55<br />

(68) (77) (86) (95) (104) (113) (122)(°F)(131)<br />

Ambient temperature<br />

100<br />

95<br />

90<br />

G_D<strong>21</strong>1_EN_00005b<br />

1.00<br />

0.95<br />

0.90<br />

85<br />

0.85<br />

0 1000 2000 3000 m 4000<br />

(3281) (6562) (9843) (ft) (13124)<br />

Installation altitude above sea level<br />

100<br />

90<br />

80<br />

G_D<strong>21</strong>1_EN_00006b<br />

1.0<br />

0.9<br />

0.8<br />

70<br />

0.7<br />

0 1000 2000 3000 m 4000<br />

(3281) (6562) (9843) (ft) (13124)<br />

Installation altitude above sea level<br />

Derating factor k I<br />

Derating factor k U<br />

Voltage derating dependent on installation altitude<br />