Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SINAMICS S120 drive system<br />
Line Modules and line-side components<br />
Active Line Modules in chassis format<br />
© <strong>Siemens</strong> AG <strong>2013</strong><br />
3<br />
■ Selection and ordering data<br />
Rated power<br />
Active Line Module<br />
in chassis format<br />
kW (HP)<br />
Order No.<br />
Line voltage 380 ... 480 V 3 AC<br />
132 (200) 6SL3330-7TE32-1AA3<br />
160 (225) 6SL3330-7TE32-6AA3<br />
235 (350) 6SL3330-7TE33-8AA3<br />
300 (450) 6SL3330-7TE35-0AA3<br />
380 (550) 6SL3330-7TE36-1AA3<br />
450 (600) 6SL3330-7TE37-5AA3<br />
500 (700) 6SL3330-7TE38-4AA3<br />
630 (800) 6SL3330-7TE41-0AA3<br />
800 (1000) 6SL3330-7TE41-2AA3<br />
900 (1150) 6SL3330-7TE41-4AA3<br />
Line voltage 500 ... 690 V 3 AC<br />
560 6SL3330-7TG35-8AA3<br />
800 6SL3330-7TG37-4AA3<br />
1100 6SL3330-7TG41-0AA3<br />
1400 6SL3330-7TG41-3AA3<br />
Accessories<br />
Warning labels in 30 languages 6SL3166-3AB00-0AA0<br />
This set of foreign language warning<br />
signs can be placed on top of the<br />
standard English or German signs.<br />
A set of signs is supplied with the units.<br />
One sign in each of the following<br />
languages is provided in each set:<br />
BG, CN, CZ, DE, DK, EE, ES, FI, FR,<br />
GB, GR, HU, IE, IS, IT, JP, KR, LT, LV,<br />
MT, NL, NO, PL, PT, RO, RU, SE, SI,<br />
SK, TR<br />
SINAMICS/SINUMERIK/SIMOTION 6SL3066-4CA00-0AA0<br />
dust-proof blanking plugs<br />
(50 units)<br />
For DRIVE-CLiQ port<br />
■ Characteristic curves<br />
Overload capability<br />
G_D<strong>21</strong>1_EN_00036b<br />
max_DC<br />
1.5 x H_DC<br />
rated_DC<br />
H_DC<br />
High overload<br />
5 s<br />
60 s<br />
300 s<br />
■ Characteristic curves (continued)<br />
Derating characteristics<br />
Derating factor k T<br />
1.3<br />
1.2<br />
1.1<br />
1.0<br />
0.9<br />
Current derating dependent on ambient temperature<br />
Note: A derating factor k T > 1.0 is to be taken into account only<br />
in conjunction with "current derating dependent on installation<br />
altitude".<br />
See also chapter System description – Dimensioning.<br />
Permissible continuous current in %<br />
of rated current<br />
Current derating dependent on installation altitude<br />
Permissible input voltage in %<br />
of rated voltage<br />
G_D<strong>21</strong>1_EN_00004c<br />
0.8<br />
20 25 30 35 40 45 50 °C 55<br />
(68) (77) (86) (95) (104) (113) (122)(°F)(131)<br />
Ambient temperature<br />
100<br />
95<br />
90<br />
G_D<strong>21</strong>1_EN_00005b<br />
1.00<br />
0.95<br />
0.90<br />
85<br />
0.85<br />
0 1000 2000 3000 m 4000<br />
(3281) (6562) (9843) (ft) (13124)<br />
Installation altitude above sea level<br />
100<br />
90<br />
80<br />
G_D<strong>21</strong>1_EN_00006b<br />
1.0<br />
0.9<br />
0.8<br />
70<br />
0.7<br />
0 1000 2000 3000 m 4000<br />
(3281) (6562) (9843) (ft) (13124)<br />
Installation altitude above sea level<br />
Derating factor k I<br />
Derating factor k U<br />
Voltage derating dependent on installation altitude<br />
3/128 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>