SINAMICS S120 drive system<br />
Line Modules and line-side components<br />
Active Line Modules in booksize format<br />
© <strong>Siemens</strong> AG <strong>2013</strong><br />
3<br />
■ Technical specifications (continued)<br />
Line voltage<br />
Active Line Module in booksize format<br />
380 … 480 V 3 AC<br />
Internal air cooling 6SL3130-... 7TE<strong>21</strong>-6AA3 7TE23-6AA3 7TE25-5AA3 7TE28-0AA3 7TE31-2AA3<br />
External air cooling 6SL3131-... 7TE<strong>21</strong>-6AA3 7TE23-6AA3 7TE25-5AA3 7TE28-0AA3 7TE31-2AA3<br />
Cold plate cooling 6SL3136-... 7TE<strong>21</strong>-6AA3 7TE23-6AA3 7TE25-5AA3 7TE28-0AA3 7TE31-2AA3<br />
Liquid cooling 6SL3135-... – – – – 7TE31-2AA3<br />
Feed/feedback power<br />
• Rated power P rated<br />
- At 380 V 3 AC<br />
- At 460 V 3 AC 5) kW<br />
(HP)<br />
16<br />
(18)<br />
36<br />
(40)<br />
55<br />
(60)<br />
80 (64 1) )<br />
(100 (75 1) )<br />
120 (84 1) )<br />
(150 (100 1) )<br />
• For S6 duty P S6 (40 %) kW <strong>21</strong> 47 71 106 (85 1) ) 145 (116 1) )<br />
• P max kW 35 70 91 (110) 2) ) 131 175<br />
DC link current<br />
• At 600 V DC A 27 60 92 134 200<br />
• For S6 duty (40 %) A 35 79 1<strong>21</strong> 176 244<br />
•Maximum A 59 117 152 (176 2) ) <strong>21</strong>8 292<br />
Input current<br />
• Rated current<br />
A 26/25/<strong>21</strong> 58/55/46 88/84/70 128/122/102 192/182/152<br />
at 380/400/480 V 3 AC<br />
• For S6 duty (40 %)<br />
A 32 71 108 161 220<br />
at 400 V<br />
• At 400 V max. A 54 107 139 (168 2) ) 200 267<br />
Current requirement<br />
A 1.1 1.5 1.9 2.0 2.5 (2.1 3) )<br />
24 V DC electronics<br />
power supply, max.<br />
Current carrying capacity<br />
• 24 V DC busbars A 20 20 20 20 20<br />
• DC link busbars A 100 200 200 200 200<br />
DC link capacitance<br />
• Active Line Module μF 710 1410 1880 2820 3995<br />
• Drive line-up, max. μF 20000 20000 20000 20000 20000<br />
Internal/external air cooling<br />
• Power loss 4)<br />
- Total power loss for<br />
kW 0.29 0.67 0.95 1.39 2.26<br />
cooling types:<br />
internal air cooling,<br />
external air cooling;<br />
cold plate cooling,<br />
liquid cooling<br />
- With external air cooling, kW 0.09/0.2 0.17/0.5 0.25/0.7 0.3/1.0 0.55/1.71<br />
int./ext.<br />
• Cooling air requirement m 3 /s (ft 3 /s) 0.016 (0.565) 0.031 (1.095) 0.044 (1.554) 0.144 (5.085) 0.144 (5.085)<br />
• Sound pressure level dB < 60 < 65 < 60 < 75 < 75<br />
L pA (1 m)<br />
Cold plate cooling<br />
• Power loss, int./ext. 4) kW 0.07/0.<strong>21</strong> 0.13/0.52 0.19/0.74 0.3/1.1 0.46/1.8<br />
• Thermal resistance R th K/W 0.075 0.055 0.05 0.028 0.028<br />
1) In the case of cold plate cooling, derating is necessary due to heat transfer to the external heat sink.<br />
2) Higher peak power is possible in combination with the Active Interface Module 6SL3100-0BE25-5AB0 (for operating cycle constraints,<br />
see SINAMICS S120 Manual).<br />
3) For 6SL3135-7TE31-2AA3.<br />
4) Power loss of Active Line Module at rated output including losses of 24 V DC electronics power supply.<br />
5) Nominal HP ratings are provided for ease of assigning components only. The Line Module outputs are dependent on the Motor Module loading and are to be<br />
dimensioned accordingly.<br />
3/112 <strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong>