Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
Catalog PM 21 2013 - Siemens Industry, Inc.
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
■ Overview<br />
© <strong>Siemens</strong> AG <strong>2013</strong><br />
SINAMICS S120 drive system<br />
Load-side power components<br />
Motor reactors for chassis format<br />
Motor reactors reduce the voltage loading on the motor<br />
windings. At the same time, the capacitive charge/discharge<br />
currents that place an additional load on the power unit when<br />
long motor cables are used are reduced. The maximum<br />
permissible output frequency when a motor reactor is used<br />
is 150 Hz.<br />
The motor reactor must be installed as close as possible to the<br />
Motor Module or Power Module. Up to 2 motor reactors can be<br />
connected in series.<br />
3<br />
■ Technical specifications<br />
DC link voltage 510 ... 720 V DC<br />
or line voltage 380 … 480 V 3 AC<br />
Motor reactor (for pulse frequencies of 2 kHz to 4 kHz)<br />
6SL3000-<br />
2BE32-1AA0<br />
6SL3000-<br />
2BE32-6AA0<br />
6SL3000-<br />
2BE33-2AA0<br />
6SL3000-<br />
2BE33-8AA0<br />
6SL3000-<br />
2BE35-0AA0<br />
Rated current A <strong>21</strong>0 260 310 380 490<br />
Rated inductance μH 53 40 24 <strong>21</strong> 19<br />
Power loss kW 0.486 0.5 0.47 0.5 0.5<br />
Line/load connection<br />
Flat connector<br />
for M10 screw<br />
Flat connector<br />
for M10 screw<br />
Flat connector<br />
for M10 screw<br />
Flat connector<br />
for M10 screw<br />
Flat connector<br />
for M12 screw<br />
PE connection M8 screw M8 screw M8 screw M8 screw M8 screw<br />
Max. cable length between<br />
motor reactor and motor<br />
(number of reactors in series) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2)<br />
• Shielded m (ft) 300<br />
(984)<br />
525<br />
(1722)<br />
300<br />
(984)<br />
525<br />
(1722)<br />
300<br />
(984)<br />
525<br />
(1722)<br />
300<br />
(984)<br />
525<br />
(1722)<br />
300<br />
(984)<br />
525<br />
(1722)<br />
• Unshielded m (ft) 450<br />
(1476)<br />
787<br />
(2582)<br />
450<br />
(1476)<br />
787<br />
(2582)<br />
450<br />
(1476)<br />
787<br />
(2582)<br />
450<br />
(1476)<br />
787<br />
(2582)<br />
450<br />
(1476)<br />
Degree of protection IP00 IP00 IP00 IP00 IP00<br />
Dimensions<br />
• Width mm (in) 300 (11.8) 300 (11.8) 300 (11.8) 300 (11.8) 300 (11.8)<br />
•Height mm (in) 285 (11.2) 315 (12.4) 285 (11.2) 285 (11.2) 365 (14.4)<br />
•Depth mm (in) 257 (10.1) 277 (10.9) 257 (10.1) 277 (10.9) 277 (10.9)<br />
Weight, approx. kg (lb) 66 (145) 66 (145) 66 (145) 73 (161) 100<br />
(220)<br />
Approvals, according to cURus cURus cURus cURus cURus<br />
Suitable for<br />
Single Motor Module<br />
chassis format<br />
Type 6SL3320-<br />
1TE32-1AA3<br />
6SL3320-<br />
1TE32-6AA3<br />
6SL3320-<br />
1TE33-1AA3<br />
6SL3320-<br />
1TE33-8AA3<br />
6SL3320-<br />
1TE35-0AA3<br />
Suitable for<br />
Power Module<br />
in chassis format<br />
• Rated current<br />
of Motor Module<br />
or Power Module<br />
• Type rating<br />
of Motor Module<br />
or Power Module<br />
Type<br />
6SL3310-<br />
1TE32-1AA3<br />
6SL3310-<br />
1TE32-6AA3<br />
6SL3310-<br />
1TE33-1AA3<br />
6SL3310-<br />
1TE33-8AA3<br />
A <strong>21</strong>0 260 310 380 490<br />
6SL3310-<br />
1TE35-0AA3<br />
kW (HP) 110 (150) 132 (200) 160 (250) 200 (300) 250 (400)<br />
787<br />
(2582)<br />
<strong>Siemens</strong> <strong>PM</strong> <strong>21</strong> · <strong>2013</strong><br />
3/203